3/8"
3/4"
Figure 10
12. FOR ALL CABLES:
Insert the bared ends of the conductors into two adjacent open-
ings in the terminal block. Tighten screws firmly to hold con-
ductors in place. See Figure 12.
13. FOR RTAS ONLY:
Remove the screw and collar from the NORMALLY CLOSED
terminal of the thermostat. Discard the collar. Push the screw
through the opening in the connector attached to the insulated
wire and screw it back into the normally closed terminal. See
Figure 13.
14. FOR ALL CABLES:
Connect conduit hub (Chromalox CCH-1 or equal) to the box.
Attach conduit to hub and bring eight inches of power leads
into the box. See Figure 14.
Figure 13
15. FOR ALL CABLES:
Strip a 3/8 inch length of each conductor of the power wiring.
Crimp the ring connector onto the end of the "Hot" conductor.
See Figure 15.
16. FOR RTAS ONLY:
Remove the screw and collar from the COMMON terminal.
Discard the collar. Push the screw through the opening in the
ring connector. Drive the screw back into the COMMON ter-
minal. See Figure 16.
INSTALLATION
Figure 11
Figure 12
Figure 14
Figure 15
17. FOR RTAS ONLY:
Insert the bared end of the ground wire into the opening of the
terminal block which is opposite of the braid (or is empty).
Insert the ends of the other hot (or neutral) and the eight inch
long wire into the two remaining openings in the terminal
block. Tighten screws firmly to hold conductors in place. See
Figure 17.
18. FOR RTAS-EP ONLY:
Slide the bared end of the hot power lead into the opening in
the terminal block which is opposite of the empty terminal.
Slide the bared end of the other hot or the neutral power lead
into the middle opening of the terminal block. Tighten the
screws firmly to hold the wires in place. See Figure 18.
19. FOR RTAS-EP ONLY:
A. Slide the bared end of the black (NORMALLY CLOSED) ther-
mostat wire into the opening of the terminal block which is
next to the incoming power leads.
B. Slide the bared end of the purple (COMMON) thermostat wire
into the opening opposite of the hot power lead. Tighten the
screws firmly to hold the wires in place. See Figures 19A and 19B.
Figure 16
Ground Wire
Figure 17
Figure 18