AC Controls
Reduced Voltage Starters — Electromechanical
Auto Transformer Starter
Operation
At starting, the auto transformer reduces
motor terminal voltage to 50, 65, or 80
percent of line voltage. For a timed inter-
val, a segment of the transformer coil is
connected in series (as an inductor) with
the motor. Then a contactor automatically
connects the motor across the line and
shorts out the inductor.
Auto Transformer Starter
Typical Speed Torque Curves
Table 15.35
Comparison of Various Electromechanical Methods
of Reduced Voltage Motor Starting
Characteristics
Starting current drawn from line as % of
that which would be drawn upon full
voltage starting
Starting torque developed as % of that
which would be developed on full
voltage starting
15
Smoothness of acceleration
Allowable accelerating times (typical)
Closed Transition.
Full voltage start usually draws between 500% and 700% of full load.
Approximate values only. Exact values may be obtained from motor manufacturer.
Solid state starters provide the smoothest starting characteristics.
306
Wye Delta Starter
Operation
Initially the starter connects the motor
on a Wye connection, reducing voltage
across the winding to approximately
58 percent. Starting torque and current
is about 33 percent of across the line.
After a time delay the motor is
connected Delta.
Wye Delta Starter
Reduced Voltage Starting
Autotransformer
Part Winding
50%
65%
80%
Tap
Tap
Tap
2 Step
25%
42%
64%
64%
Increased slightly with
45%
speed
First in order of
Third in order of
smoothness
smoothness
30 seconds
2-3 seconds
Based on NEMA
Limited by
medium duty
motor design
transformers
Siemens Electrical Products and Systems
Specification Guide
Part Winding Starter
Operation
Part winding starters apply starting
current in timed steps to part winding
motors. Two step controllers apply volt-
age through one starter to one motor
winding followed by the second starter
which connects voltage to the second
winding. The timer may be adjusted to
automatically close the second controller
at the most favorable time to minimize
voltage fluctuations.
Part Winding Starter
Wye(Star) Delta
33%
33%
Second in order of
smoothness
45-60 seconds
Limited by
motor design
General
CSI Section 16160