Alpha Group OutBack Power EnergyCell 200PLC Посібник користувача - Сторінка 5

Переглянути онлайн або завантажити pdf Посібник користувача для Аксесуари для фотоапаратів Alpha Group OutBack Power EnergyCell 200PLC. Alpha Group OutBack Power EnergyCell 200PLC 20 сторінок.

Alpha Group OutBack Power EnergyCell 200PLC Посібник користувача

Audience

This manual is intended for use by anyone required to install and operate this battery. Be sure
to review this manual carefully to identify any potential safety risks before proceeding. The
owner must be familiar with all the features and functions of this battery before proceeding.
Failure to install or use this battery as instructed in this manual can result in damage to the
battery that may not be covered under the limited warranty.

EnergyCell PLC

The EnergyCell PLC (pure-lead carbon) uses pure lead plate construction combined with
carbon additives to obtain maximum cycle life, float life, shelf life (18 months at 25°C), and
PSoC operation. The PLC is ideally suited for the three primary applications where OutBack
inverters are used: Off-Grid, Grid-Tied Battery Backup, and Grid-Tied Self Consumption.
o
Low self-discharge
Oxygen recombination efficiency: ≥ 97%
o
o
3D plate structure, optimal plate design provides better performance for high power output than
other EnergyCell models
o
VRLA maintenance free battery type
o
UL94-V0 flame-retardant jar container
Terminal
900-0227-01-00 Rev A
22.0" (55.9 cm)
Carrying
Handle
Cover
Figure 1
EnergyCell 200PLC

Introduction

4.9"
(12.6 cm)
12.6"
(32.0 cm)
5