5d) Wiring Diagram
RZ-24 in an Ex-Proof
Hold-Open System
With Door Operator
for Opening
Safe area
Central
unit
RZ-24
* Each ex-magnet has to be individually fused, with the fuse installed upstream of the magnet.
You can find more information in the manual of the magnets.
On site, the integration of a gas warning system must be checked by the ATEX representative
on the basis of explosion protection guidelines.
** Please refer to the Zener barrier manual for the detailed connection diagram.
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20220325
Electrical Connection and Installation of an Ex-Proof
Hold-Open System with RZ-24 - cont.
The following wiring examples apply when the components of points 3b
and 6 are used. If for example other fire detectors (e.g. for installation
outside the hazardous area) are used, please contact us.
A hand release switch mounted outside the hazardous area, has to
be connected so that the Zener barrier is placed between it and the
hazardous area.
IMPORTANT: In case of an alarm the RZ-24 will completely electrically
isolate the control system of the door operator!
230 VAC
supply of the door
operator controller
AR* = cutoff relay
for door operator
Fuse*
7
Zener barrier
Z779**
Hazardous area zones 1 - 2
If necessary,
Up to 12 electromagnets
2 ex-proof
EM GD 50 EX or EM GD 70 EX
CLOSE switches
Ex-proof hand
release
switch
700232
Screening, optional
(operational earth)
Technical Manual
RZ-24 Central
Max. 20 intrinsically safe
RM 3000IS EX smoke detectors or
WM 3000IS EX heat detectors
Resistor 3.9 kΩ in
the last detector
Page 07.021.13
of the line
Ill. 6a