FHF Aiza AXL05 Посібник - Сторінка 3
Переглянути онлайн або завантажити pdf Посібник для Морське обладнання FHF Aiza AXL05. FHF Aiza AXL05 6 сторінок. Sounder and sounder-strobe-combination

Sound selection table
First and Second Stage
1 Alternate two-tone
2 Alternate two-tone
3 Alternate fast two-tone
4 Alternate fast two-tone
5 Alternate two-tone
6 Alternate two-tone
7 Alternate v. fast two-tone
8 Alternate v. fast two-tone
9 Alternate two-tone
10 Continuous tone
11 Continuous tone
12 Continuous tone
13 Continuous tone
14 Continuous tone
15 Interrupted tone
16 Interrupted tone
17 Interrupted tone
18 Interrupted tone
19 Interrupted tone
20 Interrupted tone
21 Interrupted tone
22 Interrupted tone
23 Interrupted tone
24 Interrupted tone
25 Int. fast rising volume
26 Fast siren
27 Rising constant, fall
28 ISO 8201 Evacuation
29 Fast whoop
30 Slow whoop
31 Reverse sweep
32 Siren
The PFEER sound signals recommended by UKOOA are:
General Alarm Sound signal 15 Interrupted tone 1000 Hz
PAPA
Sound signal l 31 Reverse Sweep 1200 - 500 Hz
Toxic gas
Sound signal 11 Continuous tone 1000 Hz
Frequency /
Rept.
Hz
rate
800 - 1000
0.5
2500 - 3100
0.5
800 - 1000
0.25
2500 - 3100
0.25
440 - 554
0.4/0.1
430 - 470
1.0
800 - 1000
0.13
2500 - 3200
0.07
440 - 554
2.0
700
-
1000
-
1000
-
2300
-
440
-
1000
2.0
420
1.25
1000
0.5
2500
0.25
2500
0.5
700
6/12
1000
1.0
700
4.0
700
0.25
720
0.7/0.3
1400
0.25
250 - 1200
0.085
1000
10/40/10
800 - 1000
as std
500 - 1000
0.15
500 - 1200
4.5
1200 - 500
1
500 - 1200
3.0
Switch settings: ON=1 und OFF=0
Switches
Special
1 2 3 4 5
Application
1 1 1 1 1
Fire Alarms
0 1 1 1 1
Security Alarms
1 0 1 1 1
Increased urgency
0 0 1 1 1
Security deterrent
1 1 0 1 1
AFNOR, France
0 1 0 1 1
1 0 0 1 1
0 0 0 1 1
1 1 1 0 1
Turn-out, Sweden
0 1 1 0 1
All-clear, Sweden
1 0 1 0 1
0 0 1 0 1
1 1 0 0 1
0 1 0 0 1
1 0 0 0 1
0 0 0 0 1
AS2220, Australia
1 1 1 1 0
0 1 1 1 0
1 0 1 1 0
0 0 1 1 0
Pre-vital mess, Sweden
1 1 0 1 0
0 1 0 1 0
Air-raid, Sweden
1 0 0 1 0
Local warning, Sweden
0 0 0 1 0
Industrial alarm, Germany
1 1 1 0 0
0 1 1 0 0
1 0 1 0 0
Industrial alarm, Germany
0 0 1 0 0
Int. evacuation alarm
1 1 0 0 0
0 1 0 0 0
Evacuation, The Netherlands
1 0 0 0 0
Evacuation, Germany
0 0 0 0 0
Warning: Loud alarm sound. Wear ear defenders when
testing, installing and commissioning. High voltages are
present within the beacon when operational.
3