ELECTRICAL CONNECTIONS

NOTE: The emergency driver must be fed from
the same branch as the AC Driver.
STEP 1:
Remove the cover of the junction box and bring in appropriate
power supply to the junction box using one of the knock-outs.
See Figure 3.
STEP 2:
Using customer supplied 90°C minimum rated wire
connectors, make the following electrical connections:
a. Connect the black luminaire lead to the
unswitched voltage supply lead.
b. Connect the white luminaire lead
to the neutral supply lead.
c. Connect ground wire lead to the supply ground lead.
STEP 3:
Locate the two red leads in the junction box and connect them.
STEP 4:
Push all leads into the junction box. Reattach junction box
cover that was removed in Step 1 , make sure no wires are
pinched.
ZRMT TROFFER
1. SUITABLE FOR DAMP LOCATIONS.
4 ACCESS ABOVE CEILING REQUIRED. .
5 TYPE NON-IC. INHERENTLY PROTECTED.
6 CAUTION - RISK OF SHOCK. DISCONNECT POWER BEFORE
SERVICING.
9 SUITABLE FOR OPERATION IN AMBIENT NOT EXCEEDING 35°C.
10 This Luminaire complies with part 15 of the FCC Rules. Operation
is subject to the following two conditions: 1. It may not cause harmful
interference. 2. It must accept any interference received, including
interference that may cause undesired operation. CAN ICES-005 (A)/
NMB-005
11 CAUTION - RISK OF SHOCK - DO NOT INSTALL INSULATION WITHIN
76 mm (3in) OF ANY PART OF THE LUMINAIRE E.
12 MIN. 75°C SUPPLY CONDUCTORS.
ZRMT EB
1. MAX. MOUNTING HEIGHT: 15 FT. SUITABLE FOR USE IN 35C AMBIENT
TEMPERATURE.
2 Risk of Electric Shock. SUITABLE FOR DAMP LOCATIONS. IP20 TYPE
IC. INHERENTLY PROTECTED. ACCESS ABOVE CEILING REQUIRED.
4 EMERGENCY OPERATION: 90 MINUTES. CAUTION - SEE INSTRUCTION
MANUAL FOR INSTALLATION, OPERATING, AND MAINTENANCE
© 2020 Cree Lighting, A company of IDEAL INDUSTRIES. All rights reserved. For informational purposes only. Content
is subject to change. See www.creelighting.com/warranty for warranty and specifications. Cree
are registered trademarks a of Cree, Inc. SmartCast
INDUSTRIES.
5 of 5
, is a registered trademark of Cree Lighting, A company of IDEAL
®
** NOTE: DO NOT mate leads until installation
is complete and AC power is supplied
INSTRUCTIONS. MIN 75°C SUPPLY CONDUCTORS.
5 CAUTION - SERVICE BY QUALIFIED PERSONNEL ONLY. DE-ENERGIZE
BEFORE OPENING.
7 CAUTION - RISK OF SHOCK - DO NOT INSTALL INSULATION WITHIN 76
mm (3in) OF ANY PART OF THE LUMINAIRE
8 This Luminaire complies with part 15 of the FCC Rules. Operation
is subject to the following two conditions: 1. It may not cause harmful
interference. 2. It must accept any interference received, including
interference that may cause undesired operation. CAN ICES-005 (A)/
NMB-005.
10 This equipment is not self-testing in conformance with the Life Safety
Code, ANSI/NFPA 101. CSA C22.2 NO. 141 EMERGENCY LIGHTING
EQUIPMENT.
11 CAUTION - THIS UNIT HAS MORE THAN ONE POWER SUPPLY
CONNECTION POINT. TO REDUCE THE RISK OF ELECTRIC SHOCK,
DISCONNECT BOTH THE BRANCH CIRCUIT BREAKER/FUSES AND THE
EMERGENCY POWER SUPPLY BEFORE SERVICING.
CCEA APPROVED
Contains FCC ID: 2ACQ6-WIM Contains IC: 11481A-WIM
and the Cree logo
®
LUMINAIRE
GROUND
NEUTRAL
WHITE
UNSWITCHED HOT
BLACK
**RED
**RED
www.creelighting.com
LPN00696X0001A0_A