Siemens SSB81U Технічні інструкції - Сторінка 3

Переглянути онлайн або завантажити pdf Технічні інструкції для Контролер Siemens SSB81U. Siemens SSB81U 5 сторінок. Ssb electronic valve actuator, 24 vac 3-position (floating) control

Siemens SSB81U Технічні інструкції
Powermite 599 MZ Series SSB Electronic Valve Actuator
24 Vac 3-position Control

Operation

Mounting and
Installation
Wiring
Siemens Building Technologies, Inc.
A 24 Vac control signal to the Y1 extends the actuator output shaft.
A 24 Vac control signal to the Y2 retracts the actuator output shaft.
The stroke travel is proportional to the length of time the signal is applied. With no
control voltage or in the event of a power failure, the actuator maintains its last position.
NOTE:
Do not attempt to operate an actuator if it is not attached to a valve. In this
situation, the actuator will only respond to a signal on terminal Y1, and drive to
the full stroke position. It will then hold at the full stroke position.
Only by attaching the actuator to a valve, or by manually depressing the
actuator stem to engage an internal micro-switch, will the actuator respond to
a signal on terminal Y2.
Mount the actuator in one of the allowable positions shown in Figure 4.
When mounting the actuator in a plenum, the proper cable must be attached to meet
local codes.
Allow 8 inches (200 mm) above the actuator and 8 inches (200 mm) behind the cable
for service.
Installation Instructions are included with the actuator.
Do not use autotransformers. Use earth ground isolating step-down Class 2 power
supplies.
Determine supply transformer rating by summing total VA of all actuators used.
It is recommended that one transformer power no more than 10 actuators.
See Table 1 for terminal connections.
Figure 5. Terminal Connections of the SSB81U.
Figure 4. Mounting Position.
Y2
Y1
G
24
NEUT
Vac
EARTH GROUND
ISOLATING CLASS 2
TRANSFORMER FOR
24 Vac POWER
120 Vac
Technical Instructions
Document No. 155-195P25
December 18, 2003
0
1
Page 3