General
15.
On FSV c i rcuit breakers examine aramid cords to ensure
they are aligned over each of the guides ( refer to page
37 , Fig. 29 for location).
16.
Insert breaker i nto its cubicle and rack to the "discon
nect" position. Reenerg ize control power
17 .
Advance the b reaker to the "test" position and close
b reaker electrical ly. Try an opening operation. Observe
that the b reaker closes and opens.
18 .
D u ring this racking exercise note the alignment of the
stationary and movable secondary disconnects. Check
also the alig nment between the auxil iary switch bayonet
on cubicle wal l and operating yoke on b reaker. See Fig.
2a and 2b o r reference to the b reaker operating yoke.
A
A fully connected breaker controls high volt
age and currents. I mp roper use can cause
death, personal i n jury or property damage.
Perform i nitial racking to connect position on
de-energized bus. If an energized bus is un
avoid able obtain a p propriate c l earances
before beginning the next two steps.
WARNING
19.
Move breaker to fully connected position on a de-ener
g ized bus. Close and trip b reaker from main control
position.
20.
I f a lock-out key i nterlock has been p rovided, place this
interlock i n the breaker "locked out" position. key re
moved, and perform a close operation . C heck that the
b reaker has gone tri p free. Open the i n terlock, " key hel d "
position a n d repeat the closing trial . T h e breaker now
should successfu lly close.
21 .
The b reaker should now be ready for service.
Circuit Breaker Elevations
Typical front elevations and side elevations of the type MSV
and FSV Vacu u m Circuit Breakers are shown i n f i g u res 2a and
2b. The 5-MSV-250A c i rcuit breaker has a front panel d esign
43/s"
about
higher than as shown for use with type ' DG' g round
and test devices. The cubicle barrier is about
this design. The c u bicle and breaker are not i nterchangeable
without chang ing panels.
Page 5
43/s"
shorter for