DIGITEN DTC-151 Посібник - Сторінка 9
Переглянути онлайн або завантажити pdf Посібник для Терморегулятор DIGITEN DTC-151. DIGITEN DTC-151 10 сторінок.
Troubleshooting
If you have a problem with thermostat, there's usually a quick and simple
solution.
Green LED flash when power on
It is a normal phenomenon, Delay Starting Protection function for Refrigerating
Compressor is working. you could enter Setup Mode directly, or wait 3
minutes(base on DP setting value) until it doesn't flash green light before
setting the temperature controller.
Err Alarm
When temperature sensor is in short-circuited or open-circuited, the controller
will prompt sensor fault mode, and the buzzer will alarm, and LED displays
Err. Buzzer alarm could be dismissed by pressing any key. After faults solved,
the system will return to normal working mode. So make sure that the sensor
is plugged into the hole fully, if it still displays Err, you can change another
sensor.
HL Alarm
When current temperature exceeds the measuring range (less than -40°C /-40°
F or higher than 120 °C/248 ° F), the controller will prompt over-temperature
alarm mode, and cancel all the actions. The buzzer will alarm, LED displays
HL. Buzzer alarm could be dismissed by pressing any key. When temperature
returns to measuring range, the system will return to normal working status.
Heating and refrigeration equipment don't work
1.Please make sure the setting value is correct. If thermostat works fine, the
green LED(RUN) is on.
2.Please check if the loading is contacted reversely to heating or cooling
outlet.
If thermostat does not operate properly after trying the troubleshooting steps,
please send your questions to our email: [email protected].
-7-