1 Overview
The SEBB-6/24 is a supervised 24 Volt charging and monitoring system, with an
LCD display, used with the SYSTEM 3505 and emergency battery backup.
Its features include:
A 24 volt charger with a switch selection of 2 or 4 amp/hour charge rate, for a
sealed lead acid battery system. Charger selection switch should always be in the 4
amp/hour position.
An AC voltage switch to select between a 115 VAC, or a 230 VAC, 50/60 Hz. AC
Supervised. Max Input Current is 582 mA.
A supervised link with the SYSTEM 3505.
The SEBB-6/24 Mounts into any standard 19" rack, with a panel height of 3.5
inches.

2 Installation

PRECAUTIONS
2.1
CAUTION! : Do not touch internal circuitry during installation since
static discharge may damage components. If access to the interior of the
unit is required, follow the standard precautions set for handling CMOS
circuitry.

UNPACKING AND INSPECTION

2.2
Before opening, inspect the shipping container for unusual damage. Then
unpack the contents and inspect for scratches, dents, or loose internal
components.
packing material and contact the carrier immediately. Each unit has been
thoroughly inspected prior to shipment.
SEBB-6/24 CONTENTS
2.3
1. The charger (power cord is included with the charger).
2. One 6 foot length of wires with quick connects ends for battery hook up and
Molex 2 position terminal block, for the back of the SEBB-6/24.
3. One 6 foot length of wire with, a Molex 2 position terminal block for the
back of the SEBB-6/24 and with stripped ends, to attach to the Molex 2
position terminal block, located on the back of the SYSTEM 3505.
4. One 12 inch length of blue wire with quick connects ends.
5. Four installation washers (to protect the membrane panel when it is
installed on the rack).
6. One 6 foot phone cable.
DIGITIZE, INC. 700256-0001 REV. C 01/06
Specifications Subject to Change Without Notice
If your inspection reveals any physical damage, retain the