Cisco C880 E7-8800 v3 Посібник з встановлення обладнання - Сторінка 24

Переглянути онлайн або завантажити pdf Посібник з встановлення обладнання для Сервер Cisco C880 E7-8800 v3. Cisco C880 E7-8800 v3 31 сторінка.

A.1 Rack Mounting
The Cisco C880 Server (including peripheral devices) has been developed and its operation guaranteed with
the basic assumption that it is mounted in a rack. For safe use of a unit mounted in a rack, contact the
distributor where you purchased your product, or your sales representative.
When mounting the Cisco C880 Server products in a rack manufactured by another company, customers
need to confirm on their own responsibility that the rack meets the Cisco C880 Server product specifications
and requirements.
See
A.2.2 Requirements for mounting in
A.2 Rack Mounting Requirements
This section describes rack mounting requirements.
A.2.2 Requirements for mounting in a third party's rack
When mounting the Cisco C880 Server products in a rack manufactured by another company, customers
need to confirm on their own responsibility that the rack meets the Cisco C880 Server product specifications
and requirements.
Number of Check
Length of rack
Check1
Allowable spacing between
posts
Check2
Length between front post and
rear cover
Check3
Length between front post and
front cover
Width of rack
Check4
distance between the left and
right posts (common to the
front and rear posts)
Check5
Distance between holes on the
left and right device mounting
posts (common to the front
and rear posts):
Check6
Bracket installation space
Format of rack
Check7
Pitch of hole
Check8
Format and size of hole
Check9
Cable takeout port
Check10
Loading Carrying Capacity of
rack
Check11
Open area ratio of rack
Check12
Measure to prevent the rack
from toppling
.
TABLE A.1 Structural condition of rack
Term
685 to 790mm
(26.7 to 31.1 in.)
860mm(33.9 in.) or more
60mm(2.4 in.) or more
450mm(17.7 in.) or more
465mm(18.3 in) or more
(EIA standard)
There must not be interference thing
(post for reinforcement or option) in
the shaded portion of figure.
EIA standard, universal pitch
Length of each side of a square hole:
9x9(0.35 in.) to 10x10 mm (0.39 in.)
The cable can be taken out of the
bottom or rear.
Total weight must be less than
loading Carrying Capacity of rack.
Note
Loading Carrying Capacity of rack
may change when anti-earthquake
measures are given.
Open area ratio of rack of front cover
and rear cover must be more than
60%.
Measure to prevent the rack from
toppling must be performed.
21
Condition
Reference
FIGURE A.1 Length
of rack
FIGURE A.1 Length
of rack
FIGURE A.1 Length
of rack
FIGURE A.2 Width
of rack
FIGURE A.3 Format
of rack posts
FIGURE A.2 Width
of rack
FIGURE A.3 Format
of rack posts
FIGURE A.2 Width
of rack
FIGURE A.3 Format
of rack posts
FIGURE A.3 Format
of rack posts
FIGURE A.1 Length
of rack
-
-
-