Cisco ONS 15454 Встановити - Сторінка 3

Переглянути онлайн або завантажити pdf Встановити для Сервер Cisco ONS 15454. Cisco ONS 15454 32 сторінки. Four-shelf and zero-shelf bay assembly
Також для Cisco ONS 15454: Інструкція з монтажу Посібник з монтажу (22 сторінок), Встановити (32 сторінок), Розпакування та встановлення (42 сторінок), Розпакування та встановлення (40 сторінок)

Cisco ONS 15454 Встановити
Chapter 1
Install the Shelf and Backplane Cable
The following materials are required to install the optional air ramp. The number in parentheses gives
the quantity of the item included in the package:
User-Supplied Materials
The following materials and tools are required but are not supplied with the ONS 15454:
March 2005
Four 1 3/8-inch standoffs (50-1492-01)
Eight 2-inch standoffs (50-1453-01)
Four flathead screws, 6-32 x 0.5 (48-2116-01)
Standoff kit (53-0795-XX):
Plastic fiber management guides (2)
Fan filter bracket screws (53-48-0003) (6)
M4.0x 8mm, SS pan-head Phillips mounting screws (2)
Mounting brackets, 19 inch (482.6 mm), 23 inch (584.2 mm) (2)
One or more of the following equipment racks:
19-inch ANSI Standard (Telcordia GR-63-CORE) (482.6 mm) rack; total width 22 inches
(558.8 mm)
23-inch ANSI Standard (Telcordia GR-63-CORE) (584.2 mm) rack; total width 26 inches
(660.4 mm)
Fuse panel
Power cable (from fuse and alarm panel to assembly), #10 AWG, copper conductors,
194 degrees Fahrenheit (90 degrees Celsius)
If you are installing power on a 15454-SA-NEBS3E, 15454-SA-NEBS3, or 15454-SA-R1,
Note
P/N: 800-07149 shelf assembly, a #10 to #12 AWG power cable is required.
Ground cable #6 AWG stranded
If you are installing power on a 15454-SA-NEBS3E, 15454-SA-NEBS3 or 15454-SA-R1,
Note
P/N: 800-07149 shelf assembly, the #10 AWG ground cable is required.
Alarm cable pairs for all alarm connections, #22 or #24 AWG (0.51 mm² or 0.64 mm²), solid tinned
100-ohm shielded building integrated timing supply (BITS) clock cable pair #22 or #24 AWG
(0.51 mm² or 0.64 mm²), twisted-pair T1-type
Single-mode SC fiber jumpers with UPC polish (55 dB or better) for optical (OC-N) cards
Shielded coaxial cable terminated with SMB or BNC connectors for DS-3 cards
Shielded ABAM cable terminated with AMP Champ connectors or unterminated for DS1N-14 cards
with #22 or #24 AWG (0.51 mm² or 0.64 mm²) ground wire (typically about two ft [61 cm] in length)
6-pair #29 AWG double-shielded cable
Tie wraps and/or lacing cord
Labels
Required Tools and Equipment
Cisco ONS 15454 Procedure Guide, R5.0
1-3