Digiway P550 Інструкція з експлуатації - Сторінка 9

Переглянути онлайн або завантажити pdf Інструкція з експлуатації для Відкривач воріт Digiway P550. Digiway P550 15 сторінок. Sliding gate motor
Також для Digiway P550: Інструкція з експлуатації (16 сторінок)

Digiway P550 Інструкція з експлуатації
5.4 Timers setting
a) Auto close time set
Set DISP1 On, push and hold on PED for the auto close time setting. Now the red and green
LED flash fast alternatively, when reached the required time simply release PED button. Set
DIP1 OFF. The gate controller will back to working mode.
b) Lock pulse time set
Push and hold on OSC for the lock pulse time setting. Now the red and green LED flash fast
alternatively, and when gate reached the required time, simply release OSC button. Set DIP1
OFF. The gate controller will back to working mode.
5.5 SPE (special) time setting mode
To get into special setting mode, turn power off, set DIP1 on. Push and hold CLS button then turn
power on, LED will be on for short time, after LED off simply release CLS button. Gate controller is
getting into special time setting mode.
a) Reserved
Push and hold OPN reserved for late use.
b) Reserved
Push and hold PED reserved for late use.
c) PE trig close time
Push and hold on CLS for the PE trig close time setting. Now the red and green LED flash fast
alternatively and when gate reached required time, simply release CLS button.
d) Reserved
Push and hold OSC reserved for late use.

5.6 Factory default setting

Timer
Full Open Length
PED Open Length
Auto Close Time
Lock Pulse Time
Motor Stop Time
Sync Delay Time
PE Auto close Time
Reserved
To restore factory setting, turn power off and set DIP1 on, push and hold CLS button then power
on. While hold CLS button, set DIP1 off, release the CLS button. Now controller restored factory
setting from memory.
Attention: First time power up, for different working mode will be different. If in Mode-1, the
motor will run at low speed in close direction (if DIP6 is on) and hit receiving post. Next open
command gate will open at low speed until to fully opened. The controller will calculate the gate
length and compare it with original gate length. If it is right, the gate will back to normal
operation, otherwise, gate will run at low speed. If in Mode-2,3,4
P750V5.0 industrial gate motor manual
Timer Setting
F/Setting
Step
15M
0.7mm
5M
0.7mm
30 sec.
0.1sec.
0.8 sec.
0.1sec.
1.0 sec.
0.1sec.
Reserved
0.1sec.
2.0 sec
0.1sec
Reserved
0
9
Setting Method
STD& OPN Button
STD& OPN+PED Button
STD& PED Button
STD& OSC Button
SPE& OPN Button
SPE& PED Button
SPE& CLS Button
SPE& OSC Button
Range
No limitation
No limitation
0-6550sec.
0-25sec.
0-25sec.
0-25sec.
0-25sec
0