Acuity Brands Lighting AAWSC Посібник - Сторінка 10

Переглянути онлайн або завантажити pdf Посібник для Зовнішнє освітлення Acuity Brands Lighting AAWSC. Acuity Brands Lighting AAWSC 18 сторінок.

Installation Instructions
RSX LED
RSXF INTEGRAL SLIPFITTER (IS) INSTALLATION ON VERTICAL TENONS (+/- 5 °)
Note: Luminaire can be tilted up to 90 degrees (maximum) above horizontal.
Tools Required:
• 9/64" Allen Wrench
• 5/16" Allen Wrench
• 3/8" Allen Wrench
Maximum tenon/pole diameter: 2" schedule 40
pipe (2-3/8" OD)
NOTE: This luminaire is pre-wired with UL listed
supply wire leads. It is not necessary to access
fixture housing to install or wire the luminaire.
1. Remove the two (2) 8-32 splice access cover
fasteners from knuckle assembly, remove the
splice access cover, and pull supply wire leads
from knuckle cavity (See figures 13a and 13b)
2. Slip luminaire knuckle fitter over 2-3/8" Ø
pole tenon and evenly tighten the six (6) 3/8-16
UNC knuckle tenon set screws to 23-27 ft-lbs,
while maintaining the correct position of the
luminaire
3. Cut and splice the wires. Recommended cut
length is 6" for wires for ease of splicing and
securing in the knuckle
4. Make all wiring connections via the supplied
wire leads in accordance with NEC and local
codes.
5. Push all fixture and supply wires completely
within the knuckle cavity and replace the splice
access cover, gasket, and two (2) 8-32 splice ac-
cess cover fasteners.
©2016 Acuity Brands Lighting, Inc.
All Rights Reserved.
Lithonia Lighting Outdoor
One Lithonia Way, Conyers, GA 30012
Phone: 800-279-8041 Fax: 770-918-1209
www.lithonia.com
Part Number: IM-459 Rev A
Revision Date: 8/29/19
Page #8