10 Test procedure

Walk Test
Allow 2 minutes of warm up time.
Make sure that the protected area is cleared of all people.
Start walking across the detection zone.
Listen to ALARM sound whenever motion is detected (the red LED also turns ON whenever
motion is detected).
Allow 5 sec. between each test for the detector to stabilize.
Upon installation, the unit should be thoroughly tested to verify proper operation.
Walk across the entire area where coverage is desired. Should the coverage be incomplete,
readjust coverage range or relocate the detector.
Once coverage is as desired, the alarm buzzer should be disabled and the LED may be disabled.
NOTE: Walk Test procedure should be conducted, at least once a year, to confirm
proper operation and coverage of the detector.