ECI LiteWizard Посібник з монтажу - Сторінка 9

Переглянути онлайн або завантажити pdf Посібник з монтажу для Панель керування ECI LiteWizard. ECI LiteWizard 9 сторінок.

o In approximately 5 seconds (with TIMER POTs turned completely counter-clockwise)
the relays on the board should energize.
Remove or make one input invalid
o The relays should de-energize right away.
Adjust the timer(s) to the desired time remembering that with TEST LED on the times are 10% of
the actual operating time.
When complete, press the TEST button and the TEST LED should extinguish.

10 Installation Example

In the configuration shown in Figure 2- Installation Example, the timer to turn off CAB lights and fan will
start when INPUTS 1-4 are valid or ON (input LEDs lit) and Input 6 is off (Input 6 LED off). If any
input changes (any of inputs 1-4 go invalid or input 6 goes on) the TIMER resets until the inputs are
valid. Should the inputs stay valid for the configured time (set by TIMER 1 and 2 POTs) the cab lights
and fans will turn off.
LiteWizard™ Installation Manual
Figure 2- Installation Example
Electronic Controls, Inc.
7073 North Atlantic Ave. Cape Canaveral, FL 32920
800-633-9788
www.eciamerica.com
P a g e
| 9