Revised 10/10
2.1.5 PROGRAMMING
The main menu consists of Set Point 1 Low (SP 1 lo), Set Point 1 High (SP 1 hi), Set Point 2 Low (SP 2 lo), and Set
Point 2 High (SP 2 hi). SP 1 lo and SP 1 hi is the pulse cleaning for the dust collection system with SP1 lo set at 2.5 and
SP 1 hi set at 3.0. Pulse cleaning will activate at 3.0 and deactivate at 2.5. There will be an occurrence in the service
life of the filters in which the pulse cleaning will not recover at SP1 lo of 2.5 requiring a setting revision to Sp 1 lo and
SP 1 hi. A setting revision should be completed in increments of 0.5 during the service life of the filters. The next setting
of SP 1 lo would be 3.0 with SP 1 hi at 3.5. Set Point 2 Low and Set Point 2 High is an alarm range indicating filters will
require a replacement. The filters should only be replaced when process ventilation is unsatisfactory.
MENU
Main
Menu
2.1.6 OPTI-LINK ™
Opti-link™ is an infrared communications technology
that allows the user to upload and download
program parameters from one unit to another with
a programming key. By using the PK-01 universal
programming key, the user may program one
unit, download those parameters to the universal
programming key and then upload that same program
from the key to other controls. By using a PK-02 lockout
programming key, a user may completely lock (or
unlock) the face keypad of the control to eliminate the
possibility of unwanted tampering of the control.
To download programs from a control to a programming
key, place the key within 1 to 6 inches of the Opti-
Link™ port on the control and hold the two outside
buttons simultaneously until the numeric LED on the
control turns off. The programming key should stay
within the 1 to 6 inch range while the download is in
progress. During the operation, the Process Arch on the
control will give the status of the download. When the
download is complete, the programming key will blink
green twice to indicate the program is stored on the
programming key.
To upload programs from a programming key to a
control, place the key within 1 to 6 inches of the Opti-
Link™ port on the control and hold the center button
until the numeric LED on the control turns off. The
programming key should stay within the 1 to 6 inch
range while the download is in progress. During the
operation, the Process Arch on the control will give the
status of the download. When the upload is complete,
the control will read "yes" to indicate the program has
been successfully uploaded to the control.
2.2 DPM-A2
2.2.1 MODEL NUMBER CONFIGURATION
The DPM-A2 is a microprocessor based digital
pressure gauge for positive, negative and differential
measurement designed to be a direct replacement
for mechanical gauges. The 1⁄2" LCD display gives
VARIABLE
➲ Set Point 1 Low
➲ Set Point 1 High
➲ Set Point 2 Low
➲ Set Point 2 High
CODE
SP1 lo
SP1 hi
SP2 lo
SP2 hi
the gauge improved readability and precision. These
products also feature five user selectable engineering
units including in. w.c., mm w.c., cm w.c., kPa and Pa.
The DPM-A2 also has a "process arch" which gives the
gauge a similar look to mechanical gauges by giving a
continuous percent output status.
2.2.2 SPECIFICATIONS
Maximum Pressure: Ranges ≤ 4" w.c. = 2 PSI;
Ranges ≥ 5" w.c. = 10 PSI
Media compatibility: Air and compatible non-
combustible, non corrosive gasses
Accuracy: - 1.00%
Temperature Ranges:
Compensated: -10° to 140°F (-23° to 60°C)
Operating: -10° to 140°F (-23° to 60°C)
Thermal Effect: +/- 0.02% FS/°F
Output Signal: 4-20 mA (option)
Loop Resistance: 750 Ω Max (for internally sourced
power); 1800 Ω Max (for externally sourced power
of 36 VDC)
Power Supply: Universal 20-240 VAC or VDC
Housing Material: Glass Filled Nylon
Enclosure Rating: Designed to meet NEMA 4X face
Electrical Connections: screw terminals
Response Time: <100 ms
Display: 4 Digit, red LED, 1⁄2" digits;
Process Connection: Push on connection
for 3/16" tubing
Agency Approvals: ETL, CE
Pulse Control Panel
DPM/DPC
SETTING
2.5
3.0
3.5
5.0
7