FirePro 08100 Посібник - Сторінка 6

Переглянути онлайн або завантажити pdf Посібник для Панель керування FirePro 08100. FirePro 08100 10 сторінок.

FirePro 08100 Посібник
Positioning
FP Units directing the aerosol stream away from opening

Connection of Multiple FirePro Generators

5
Where multiple FirePro Generators are installed, connect using the
FP-08919 Splitter Lead.
Splitter Leads can be installed at any point on the activation. For
ease of install, servicing and efficient field wiring, Splitter Leads
should be installed in areas easy to access and minimise extension leads.
The supply voltage of any system will determine the no of FirePro units which can be used
12vDC
Where additional units are required in the system use Discharge Delay Module(s).
FP Unit 1
FP Unit 1
FP Unit 2
CORRECT
Max = 2 FP Units
Connection of 2 FirePro Units
Extension Lead
Connection of 4 FirePro Units
FP Unit 3
FP units are directing the stream towards the opening.
24vDC
FP
Unit
2
Extension Lead
FP Unit 4
Control Panel
Model 08100
INCORRECT
Max = 4 FP Units
Activation
Splitter
Lead
Splitter Lead
Activation
Cable
Rev 4.0
Cable
Page | 6