Fireray 5000 Посібник користувача - Сторінка 16

Переглянути онлайн або завантажити pdf Посібник користувача для Димова сигналізація Fireray 5000. Fireray 5000 17 сторінок. Motorised infrared optical beam smoke detector

Fireray 5000 Посібник користувача

21. Technical Specifications

Parameter
Operating Voltage
Operating Current –
Operating Current –
Fire Threshold Range
Delay to Fire
Delay to Fault
Operating Distance between Detector and Reflector
Maximum angular misalignment of Detector
Maximum angular misalignment of Reflector
Maximum angular movement of Detector head
Optical wavelength
Rapid Obscuration Fault threshold
Operating Temperature (UL Approved)
Operating Temperature (EN54-12 Approved)
Operating Temperature (FM Approved)
Storage temperature
Relative Humidity (non condensing)
IP Rating
Relay Contact Rating
Maximum Cable Length (Controller to Detector)
Cable Gauge
Housing Flammability rating
Dimensions
System Controller, including base
Detector, including 'easy fit' base
Reflector (Single)
Document Number: 0044-033-05-EN
Normal Operation
(including fire or fault activated)
Alignment modes - HiA
Alignment modes - LoA
Width,
mm (in)
202 (8.0) 230 (9.1) 81 (3.2)
135 (5.3) 135 (5.3) 135 (5.3) 0.5 (1.1)
100 (3.9) 100 (3.9) 10 (0.4)
16
Value
14—36V DC
5.5mA - 1 Detector
8mA - 2 Detectors
36mA
5.5mA / 8mA
0.45—3.98 dB
10—60%
2—30 s
2—30 s
8—100 m
± 0.3 Deg
± 5 Deg
± 3.5 Deg
850 nm
87%
0—+37.8 Deg C
-10—+55 Deg C
-20—+55 Deg C
-40—+85 Deg C
93%
IP54
VFCO, 2A@30VDC
Resistive
100 m
24—14 AWG
0.5—1.6 mm
UL94 V0
Height,
Depth,
mm (in)
mm (in)
Weight,
kg (lb)
1.0 (2.2)
0.1 (0.2)