CALEFFI 161010 Посібник - Сторінка 10

Переглянути онлайн або завантажити pdf Посібник для Контролер CALEFFI 161010. CALEFFI 161010 20 сторінок. Heating controller

Factory
Range
setting
Corr.tMixer
90 s
5 ... 300 s
tPLAY
4 s
1 ... 15 s
Block. prot.
Yes
Yes, No
PWM
Heating
Heating, Solar
Slab drying
-
-
TStart
20 °C
10 °C ... 30 °C
TMax
45 °C
20 °C ... 60 °C
Rise
5 K
1 ... 10 K
Rise time
24 h
1 ... 24 h
tBacking
7 d
1 ... 20 d
Start
-
Start, Cancelled Activation / Deactivation slab drying
Language
Italiano
Deutsch, English,
Francais, Italiano
Reset
No
Yes, No
Operation
0
0 ... 9999
Pump
-
0 ... 9999
Mixer open
-
0 ... 9999
Mixer closed
-
0 ... 9999
Backup heating
-
0 ... 9999
Max. S1
-
max. 999.9 °C
Max. S2
-
max. 999.9 °C
Max. S3
-
max. 999.9 °C
Min. press.
-
0.0 ... 10.0 bar
Max. press.
-
0.0 ... 10.0 bar
Version
-
-
All relays
Auto
Auto, Off
Man. 1
Auto
On, Auto, Off
Man. 2,3
Auto
Mixer
Auto,
open, Off
Man. 4
Auto
On, Auto, Off
back
10
Description
Surplus mixer runtime when the mixer is
closing
Mixer control time for change of fl ow
direction
Blocking protection option
PWM profi le PWM A
Slab drying submenu
Slab drying start temperature
Slab drying holding temperature
Slab drying rise value
Slab drying rise time
Slab drying holding time
Language selection
back to factory settings
Operating days of the controller (balance
value, cannot be set back to zero)
Balance values, can be set back to zero (see
page 16)
Display of software version
Operating modes of all relays
Manual mode relay 1
closed,
Manual mode relay 2,3
Mixer
Manual mode relay 4
5

Indications, functions and options

Note:
The display and adjustment channels as well as the adjustment ranges de-
pend on the system selected, the functions and options as well as on the
system components connected to the controller.

5.1 Home screen

The home screen is a graphic representation of the current system state.
The following indications are possible:
Standby mode
The room thermostat does not demand heating / cooling.
Heating mode in system 1 with return temperature monitoring
The room thermostat demands heat, TFcalculated = Yes.
Heating mode in system 1 without return temperature monitoring
The room thermostat demands heat, TFcalculated = No.