calentador Supreme 14e Встановлення та обслуговування - Сторінка 4
Переглянути онлайн або завантажити pdf Встановлення та обслуговування для Водонагрівач calentador Supreme 14e. calentador Supreme 14e 9 сторінок. Domestic gas water heater
SUPREME E
Connection with separate tubes
fig. 7 – Examples of connection with separate tubes ( air=
Table. 3 - Type
Type
Description
Horizontal extractor and exhaust on the wall. The inlet and outlet terminals must
C1X
be concentric or sufficiently close (maximum distance 50 cm) so that they are
exposed to similar wind conditions.
Vertical extractor and exhaust on the roof. Inlet/outlet terminals as for C12
C3X
Separate extractor and exhaust on the wall or roof, in areas of different pressure.
C5X
The extractor and exhaust must not be on opposite walls.
Extractor and exhaust with separate certified tubes (EN 1856/1)
C6X
Extractor inside the installation place and exhaust on the Wall or roof
B2X
IMPORTANT – THE LOCATION MUST HAVE APPROPRIATE VENTILATION.
To connect th e separate pipes, fit the following initial accessory in the unit:
fig. 8 - Initial accessory for separate pipes code. 010031X0 / 4740
Before installation, check the diaphragm intended to be used and check that it
does not exceed the maximum length permitted, using a simple calculation:
1.
Design the whole system of separate chimneys, including the accessories
and outlet terminals.
2.
Consult table 5 and determine the losses in
component according to the position of the installation.
3.
Check that the sum total of losses is lower than or equal to the maximum
length permitted in table 4.
Table. 4 – Diaphragms for separate pipes
Model
SUPREME 11 E
Maximum length
permitted
SUPREME 14 E
Model
SUPREME 11 E
Diaphragm indicated
SUPREME 14 E
4
steam=
m
(equivalent metres) for each
eq
SUPREME E
Length
65 m
eq
55 m
eq
Length
Diaphragm
ø 39
0 - 20 m
eq
ø 43 (mounted)
20 - 35 m
eq
>35 m
Without diaphragm
eq
0 - 20 m
ø 47 (mounted)
eq
20 - 35 m
ø 50
eq
>35 m
Without diaphragm
eq
cod. A73020280 - Rev. 01 - 02/2013
Table. 5 - Accessories
0.5 m M/H
TUBE
1 m M/H
2 m M/H
45° H/H
BEND
45° M/H
90° H/H
90° M/H
)
90° M/H + outlet to check
Ø 80
With outlet to check
SLEEVE
for condensation discharge
4 for condensation discharge
TERMINAL air on wall
Steam on wall with windproofing 1KWMA86A
Air/steam separate 80/80
CHIMNEY
Only steam outlet Ø 80
3.6 Solar system operation mode
At the unit's cold water inlet there is a contact thermostat (set at 45°C) for
controlling the solar system water temperature. This thermostat prevents lighting
of the burner when the inlet temperature is higher than the set thermostat
temperature.
A thermostatic mixing valve must be installed at the DHW outlet to prevent water
at high temperatures from being drawn.
4. SERVICE AND MAINTENANCE
All adjustment, commissioning and periodical inspection operations described
below must only be carried out by Qualified Personnel (meeting the professional
technical requirements of the current regulations).
FERROLI declines any liability for damage and/or injury caused by unqualified
and un- authorised persons tampering with the unit.
4.1
Adjustments
Gas conversion
Conversion to a gas different from the factory setting must be
done by and authorised technician, using original parts and in
compliance with the regulation in force in the country of
installation.
The unit can work on natural gas or LPG and is factory-set for use with one of
these two gases, as clearly shown on the packing and data plate. Whenever the
unit has to be used with a different gas, the special conversion kit will be
required, proceeding as follows:
•
Disconnect the ignition electrode cable.
Losses in
m
eq
Steam output
Air intake
Vertical
1KWMA38A
0.5
0.5
1KWMA83A
1
1
1KWMA06K
2
2
1KWMA01K
1.2
2.2
1KWMA65A
1.2
2.2
1KWMA02K
2
3
1KWMA82A
1.5
2.5
1KWMA70U
1.5
2.5
1KWMA16U
0.2
0.2
1KWMA55U
-
3
1KWMA05K
-
7
1KWMA85A
2
-
5
1KWMA84U
-
12
1KWMA83U +
-
4
1KWMA86U
fig. 9
Horizontal
1
2
4
-