If a long distance relocation is required, restore the rack cabinet to the configuration of the rack
cabinet as you received it. Pack the rack cabinet in the original packaging material, or equivalent.
Also, lower the leveling pads to raise the casters off of the pallet and strap the rack cabinet to the
pallet.
To move the rack cabinet to another location, complete the following general steps:
1. Follow the safety guidelines in this chapter.
2. Know the weight of the rack cabinet. To help determine the weight of the rack, see Table 2 on page 7. A
general guideline is to assume a weight of 23 kg (50 lb) per rack U-space.
3. Use the following weight limit guidelines:
If the rack cabinet is empty, at least two people are required to move the rack.
If the rack cabinet weight is between 142 and 227 kg (between 313 and 500 lb), three or four people
are required to move the rack.
If the rack cabinet weight is greater than 227 kg (500 lb), professional movers are required to move
the rack.
4. Install the outriggers on both sides of the rack cabinet.
DANGER:
Always relocate the rack cabinet with the outriggers installed. Keep the outriggers and install them if you
have to move the rack to another location in the future.
Use the wrench the comes in the hardware kit to install the four bolts that attach each outrigger to the rack
cabinet. Make sure that you tighten the bolts securely.
Note: If lower side panels are attached to the upper side covers, you must remove the lower side panels
before you install the outriggers. For more information, see
Figure 25. Installing the outriggers
Installing and removing the lower side panels.
37