8. RU NN I N G YOUR SYS TEM
Run the system at fully open, maximum temperature for 1 hour, to expel any air in the system. Release any air that may be trapped at appropriate
radiator bleed points and return manifold bleed point. Turn off TRV/flow manifold and allow to cool. Set to desired room setting and run
normally. NOTE: DiscreteHeat recommend flushing the system with ThermaSkirt Cleanser TS3 or alternatively Scalemaster SM3 (check dosage
carefully) and running with ThermaSkirt corrosion inhibitor TS5 or alternatively Scalemaster SM5 or SM10 (check dosage carefully) to
ensure maximum longevity and reliability. Hard water areas may require additional precautions. Chemically softened water must NOT be used. This is
a standard precaution for ALL wet heating systems and a requirement of BS 7593:2006. Contact DiscreteHeat for specific application advice.
Failure to provide a suitable corrosion inhibitor will invalidate your warranty!
9. TROUBL E S HOOTI NG
PROBLEM
Leak at joint.
Leak on ThemeSkirt pipes.
ThermaSkirt not hot.
Water from return manifold
Noise - ticks & clicks when heat on
Sudden 'bangs'
10. BL EE DI NG YOUR SYSTE M
As ThermaSkirt
®
acts like a pipe, in normal operation air does not get trapped. However, on existing systems, to which ThermaSkirt is added, air
may get trapped in the existing pipework to and from the skirting. Follow these simple steps if you discover cold sections of the ThermaSkirt
which do not heat up.
1. System with ThermaSkirt
Turn off all radiators and ThermaSkirt thermostatic and lockshield
valves. Make sure your system is fully pressurised and the pump is
set to max. Run the system for a few minutes, and, starting from
the lowest
point
in
radiator/ThermaSkirt system, one at a time. Run for a further 2
minutes (approx) , close again and move to the next Ther-
maSkirt or radiator, moving upwards in the house. Any air will
be expelled through the boiler or trapped in a conventional
radiator. Bleed the radiator as normal.
2. New Installation with ThermaSkirt
On installation, in a convenient place at the highest point
of the system, 'T' off into a vertical leg 600mm high and
install an automatic/manual air vent.
Following the procedure above, close and open each
ThermaSkirt
system in turn.
®
Any air forced round the system will be expelled through
the boiler or through the air vent.
Air can also be bled from the bleed screw on top of the
return manifold (A).
Tel: 0845 1238367
CAUSE
Faulty / incorrect installation.
No inhibitor fitted.
Corrosion chemical/cleaner left in system
Check boiler.
Lockshield valve closed.
TRV valve closed / off.
Air trapped in pipework.
Manifold not closed fully.
Connectors & fittings rubbing on wall.
ThermaSkirt length(s) cut too long,
expanding and jumping off the bracket.
Internal corners clipped both sides.
®
& Conventional Radiators.
the
house,
open
each
Only.
®
Fax: 01942 665104 e-mail: [email protected] web: www.discreteheat.co.uk
TM
I N S T A L L AT I O N
Trapped air expelled through boiler
Auto vent recommended to ease bleeding
AV
SOLUTION
Drain and replace fitting or 'O" ring from spares kit.
Drain down, cleanse with TS3 and install inhibitor TS5.
Drain down, replace piece, cleanse with TS3 and refill.
Is heating 'ON' and pressure OK?
Open Lockshield valve (
).
Open TRV valve (
).
See 10 below.
Turn to 'OFF' position.
Relieve plasterwork at Feed & Return and/or corner fittings.
Check lengths & refit if necessary.
Check & remove/unclip unecessary clip.
600mm (min)
Trapped air expelled through boiler
Page 8
®
®
CLOSE
CLOSE
TRV Unit
A