Distech Controls Allure ECB-103 Посібник з монтажу - Сторінка 12

Переглянути онлайн або завантажити pdf Посібник з монтажу для Контролер Distech Controls Allure ECB-103. Distech Controls Allure ECB-103 16 сторінок.
Також для Distech Controls Allure ECB-103: Посібник з монтажу (16 сторінок)

Distech Controls Allure ECB-103 Посібник з монтажу
7. To enter the GEN CFG submenu, press the down button
8. Press the Menu button
9. Use the up and down buttons
ommended level of sensitivity is medium (1) and should typically work with all installations. This setting should not be changed unless for some rea-
son you are experiencing false detections, then a low sensitivity (0) setting may be used, or if working with larger room installations a high sensitivity
(2) setting can be used.
10. Press the Menu button
11. Press and hold the Menu button
The motion indicator LED provides a visual confirmation of motion detection. By default, the indicator (PIR LED
jumper) is enabled. If you wish to disable it, set jumper J18 to Disabled. See Connector and Jumper Location,
Identification and Configuration [pg. 3].
BACnet Network Access from the Sensor
To temporarily access the BACnet MS/TP LAN for commissioning and maintenance purposes (not available with either the ECB-PTU series controllers,
the ECLYPSE series controllers, or the ECB-VAVS), connect a BACnet MS/TP Adaptor to the audio plug port located on the lower edge of the Allure EC
Smart Vue sensor. Wire a standard ⅛" (3.5 mm) three-conductor stereo jack as shown below.
The BACnet MS/TP Adaptor must have an electrically-isolated RS-485 port. Otherwise a ground path from the
BACnet network will be made through the computer that will disrupt BACnet network communications.
Figure 13:
⅛" (3.5 mm) Stereo Jack Connection for a Portable Router
12 / 16
several times until MOTION SENSITIVITY appears on the display. The current motion sensitivity level is shown.
Screen Timeout: 30 seconds
to set the motion sensitivity level to 0 (low), 1 (medium - typical default setting), or 2 (high). The default and rec-
once to apply the value.
for 5 seconds to exit the configuration menu.
LAN Access
Connector
NET+
NET-
Shield
Cable Supplied with
BACnet MS/TP Adaptor
To BACnet MS/TP
Adaptor
once.
OR
NET+ (White)
NET- (Red)
- Temporary
Commissioning and
Shield (bare)
Maintenance
Connection
- No EOL Resistors are
Necessary
BACnet MS/TP Adaptor
with Isolated RS-485 Port