esera automation Auto-E-Connect 11230 Посібник користувача - Сторінка 4

Переглянути онлайн або завантажити pdf Посібник користувача для Системи вводу/виводу esera automation Auto-E-Connect 11230. esera automation Auto-E-Connect 11230 6 сторінок. 4-fold analog input insulated for 1-wire bus

8
LED indicator
The module has a green LED indicator which lights up when the module is supplied with 12V operating
voltage.
Indicator
Designation
LED green
Power
9
Software / Control
The block is controlled by a 1-Wire command for the DS2450 block.
The module is internally fixed to the following parameters: Resolution: 12Bit, voltage range: 5V
Details can be taken from our example program in the shop.
10
Calculation
The following formula can be used to evaluate the analog module:
Calculation from integer raw values
DS2450_Integer = raw values in integer (0-1024)
Analog value (V) = (5.0 / 4096) * 2.004 + (DS2450_Integer)
Calculation from analog value
DS2450_Analog = raw value in Volt
Analog value (V) = DS2450_Analog * 2.004
Sample program (PHP for IP-Symcon)
The analog values are calculated using a script. For details see example script in the shop.
11
Control by 1-Wire Controller / 1-Wire Gateway
The control and data output of the 4-fold analog input via the 1-Wire Controller / 1-Wire Gateway is
simplified. The current sensor data is output continuously. No query of the data is necessary nor available.
11.1
Data output 1-Wire Controller / 1-Wire Gateway
The following data formats are output for the ESERA-Automation modules. If you divide the value by 100,
you will receive the data with two decimal places.
Data output:
1_OWD1_1|50 => Controller No._module no._Data set|Voltage 0-10V (mV) Example: 0.050V
1_OWD1_2|250 => Controller no._module no._Data set|Voltage 0-10V (mV) Example: 2.50V
1_OWD1_3|491 => Controller no._module no._Data set|Voltage 0-10V (mV) Example: 4.91V
1_OWD1_4|500 => Controller no._module no._Data set|Voltage 0-10V (mV) Example: 5.00V
Further information on the possibilities and commands can be found in the current programming manual of
the 1-Wire Controller /1-Wire Gateway, which can be found within Config Tool 3.
12
Integration in IP-Symcon / ESERA-Station
At our website we provide ESERA IP-Symcon software modules for easy integration of 4-fold analog input
into IP-Symcon via 1-Wire controller / 1-Wire gateway. No scripts are necessary anymore. Details can be
found on the ESERA website under "Compatible controllers / Central/IP-Symcon integration"
https://www.esera.de/kompatible-steuerungen-zentralen/ip-symcon-integration/
A script for the conventional connection via 1-Wire bus coupler can be found in the article download area.
Further details can be found in the example script.
13
Integration in Loxone
Via the shop we provide an example project for the reading of analog voltages via 4-fold analog input via
1-Wire Controller 1. Details see here:
https://www.esera.de/kompatible-steuerungen-zentralen/loxone-integration/demo-1-wire-controller-1-
loxone-integration/
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
Function
 Lights up permanently as an indicator for operational readiness.
11230 V2.0 R1.0 Manual