5. WIRING DIAGRAM
Here you can see the full wiring diagram. The presence/absence of analog output and
the relay size depend on the.
MEANING OF LEDs
RED LED there is an alarm. It flashes when an hotkey is detected and during the
copy of the parameters with HOTKEY;
GREEN LED It is ON during normal functioning if the device is powered correctly. It
flashes when an hotkey is detected and during the copy of the parameters with
HOTKEY;
YELLOW LED it flashes quickly if there is serial activity and when an hotkey is
detected and during the copy of the parameters with HOTKEY;
6. DEVICE CONFIGURATION
The device can communicate with the serial line only if a serial address is selected. This
setting has to be done with DIP-SWITCH. The serial address has to be arranged only in
case of using the serial line, if the programming procedure will be made by HOTKEY
this procedure can be skipped. There are 31 address available as explained by the
following table:
SELECTOR
ADDRESS
SELECTOR
ADR 1
ADR 2
ADR 4
ADR 6
ADR 8
1592030000 xh50_55p r1.2 gb 2011.06.28.doc
ADR 10
ADR 12
ADR 14
ADR 16
ADR 18
ADR 20
ADR 22
ADR 24
ADR 26
ADDRESS
ADR 1
ADR 28
ADR 3
ADR 30
ADR 5
With the selectors 6 and 7 it's possible to configure the internal/external temperature
probe. Please see the following table:
The probe used to
ADR 7
calculate the dew-point is
the internal probe
ADR 9
ADR 11
ADR 13
ADR 15
ADR 17
ADR 19
ADR 21
ADR 23
ADR 25
ADR 27
ADR 29
ADR 31
The
probe
used
to
calculate the dew-point
is the external probe
XH50-55P
The device read only the humidity
Thanks to the last selector (number 8) it's possible to select the digital input polarity. If
the selector is in ON position, the digital input is considered as active when the electrical
contact is closed, with the opposite configuration the digital input is active when the
electrical contact is opened.
7. CASE CLOSURE
After making the connections, please close the box following the procedure described
here below. As described as point
insert the cover starting from the bottom and
perform a rotation as described by point
The closing of the case is made when
you'll hear a light click
.
8. CASE OPENING
Please pay attention in order to avoid the damaging of electronic parts. In order to open
the case, you should follow the figure below
2/5