3) Remote control box (not included)
Remote control interface
4. ASSEMBLE
1. Location
First ensure that there is enough space to install the inverter, while the installation
location must meet the following requirements:
(1) Dryness: Avoid dripping water or other liquids on the inverter.
(2) Coolness: The operating temperature for the product is 32-104°F(0-40°C), the
preferable temperature is 50-77°F(10-25°C), the lower temperature is better within
this range.
(3) Ventilation: There should be a certain distance between inverter and other objects, to
avoid blocking the product's vents. Allow 2 inches (5cm)from openings.
(4) Cleanness: Do not install the product around dust, wood chips or other particles. When
the cooling fan turns on, the particles will be sucked into the inverter , thus increasing
internal temperature..
(5) When connecting inverters and batteries, it will produce arcs or sparks, so there
should not be flammable objects around, such as gasoline, alcohol, etc.
2. Mounting instructions
Mount on a solid platform because of the heavy weight, such as floor, table or stable
support. In order to avoid sliding off, the platform should bear the weight of the product,
and it is better to attach the product with four screws.
3.
13
11 / "
16
(320mm)
11
8 / "
16
(216mm)
3. Mounting the remote control box (Optional equipment)
1
3 / "
16
5
1
1 / "
2 / "
16
5
2 / "
16
1) the remote is designed to be mounted on a dash or other surface where a hole should
be cut so that it sits flush. This is not a requirement however just a recommendation.
2) The remote cable should be plugged into inverter and the remote before mounted.
Note: Optional remote is not needed for inverter operation. The main power switch will
work the power on / off.
5. Battery
1). Voltage and current of the battery
The battery is designed to supply the unit with DC input voltage and the rated
voltage should be in accordance with the rated input voltage of the inverter. Any
voltage exceeding the range of the input voltage of the inverter will cause over
voltage or under voltage protection.
Also, the battery must supply sufficient current. A small capacity battery
cannot drive a large power electrical appliance. In this case, the battery will
cause an under voltage protection because of the over-discharge of the battery.
The simple calculation method of battery current is: load power divided by
battery voltage. Due to the consumption of the inverter itself, the actual current
will be about 10% larger. For example, the voltage of a lead acid battery is
12VDC, and load power is 1000W, therefore, the actual current of the battery is
about 1000W÷12V×110%≈91.6Adc.