AIMS Power CON120AC12/24VDC Посібник користувача - Сторінка 11

Переглянути онлайн або завантажити pdf Посібник користувача для Зарядний пристрій AIMS Power CON120AC12/24VDC. AIMS Power CON120AC12/24VDC 11 сторінок. Ac converter / battery charger

4
.
3
P
r
o
t
e
c
t
i
o
n
4
.
3
P
r
o
t
e
c
t
i
o
n
Input Over Voltage
Reverse Battery Polarity Protection
Input Under-voltage
Output over voltage
12/24V mode
Charger over temperature
protection
BTS(Battery Temperature Sensing)
4
.
4
E
n
v
i
r
o
n
m
e
n
t
a
l
4
.
4
E
n
v
i
r
o
n
m
e
n
t
a
l
Operation temperature
Relative humidity
Noise
Storage Conditions Temperature
Cooling
Safety
4
.
5
M
e
c
h
a
n
i
c
a
l
4
.
5
M
e
c
h
a
n
i
c
a
l
Dimension (D x W x H) mm
Unit Weight
Gross Weight
Unit must be safe for input voltage up to 150VacRMS (and up
to 215Vpeak), need not be operating. Above this level the unit
may be damaged.
Non-destructive reverse battery polarity protection with fuses.
Unit shall not sustain damage and shall meet all specifications
after fuse replacement.
Unit must not be damaged for all input voltages from
0-300Vac. Shutdown or input current limit or other means may
be applied when input voltage is out of normal operating
range.
12Vdc. Unit will shut down if Vcharging > Vcharging (target) +
1.0Vdc for more than 2 seconds; unit will restart when voltage
<= Vcharging (target) for more than 2 seconds.
For battery OVP the unit will restart in the same stage.
24Vdc. Unit will shut down if Vcharging > Vcharging (target) +
1.5Vdc for more than 2 seconds; unit will restart when voltage
<= Vcharging (target) for more than 2 seconds.
For battery OVP the unit will restart in the same stage.
The internal temperatures of the charger will be measured by
NTC. Based on these measurements, unit will shut down if the
temperature exceeds 105°C. Unit will restart when
environment temperature cools to 95 °C.
The battery temperature sensor allows the charge controller to
continuously adjust charge voltage / charge current based on
actual battery temperature.
When the battery temperature is over 40 °C, unit will reduce
the charging voltage to Float voltage, also it will reduce the
Max charging current by 10% with every two degree of
temperature rise.
When the battery temperature is over 50 °C, unit will shut
down.
Nominal ambient temperature: 25°C
Operating Ambient Temperature range: -10°C to 40°C
(On the heat sink of DC-DC part, if the temperature is over
90 ℃, the Charger Current will be de-rate to 50% ; if the
temperature is over 105 ℃, the Unit will be shut down.)
5~95% without condensation
Unit requirements: below 50dB (A) measured at 1 m
distance with fan full working.
-20°C to +80°C
Smart fan control
UL458,CSA22.2#107.1
10.25" * 6.75" * 3.25"
6.5 lb
7 lb
- 11 -