Figure 3-3 Neutral Current Sensor Placement
NOTICE
Do not connect the neutral current sensor secondary
output to ground. Connecting the secondary output
to ground may cause damage to the trip unit.
NOTICE
The polarity of the sensor connections is critical.
Always observe the polarity markings on the instal-
lation drawings. The polarity markings are identified
as white dots on the transformer. To insure correct
ground fault equipment performance, conduct field
test to comply with National Electric Code require-
ments under article 230-95-C. See Section 5.2 for
instructions.
Install accessory(ies), if required, using appropriate
instruction leaflet listed in Section 7.2. Where acces-
sories are not required, install protective barriers sup-
plied with the trip unit in accessory retaining slots of the
trip unit.
1.50
.03
.281 Diam.
2 Holes
6.17
1.438
1.47
Ref.
4.375 Ref.
5.61
5.75
.36R
.28R
Polarity
Markings
.12R
Table 3.1 Digitrip L-Frame OPTIM Rating Plugs
Max Amps
of trip unit
125A
125A
125A
125A
125A
125A
250A
250A
250A
250A
250A
250A
250A
400A
400A
400A
400A
400A
400A
600A
600A
600A
600A
600A
I.L. 29C508B
2.188
2.25
2.33
3.04
In
Catalog Number
63 A
ORPL125A063
70 A
ORPL125A070
90 A
ORPL125A090
100 A
ORPL125A100
110 A
ORPL125A110
125 A
ORPL125A125
125 A
ORPL025A125
150 A
ORPL025A150
160 A
ORPL025A160
175 A
ORPL025A175
200 A
ORPL025A200
225 A
ORPL025A225
250 A
ORPL025A250
200 A
ORPL40A200
225 A
ORPL40A225
250 A
ORPL40A250
300 A
ORPL40A300
350 A
ORPL40A350
400 A
ORPL40A400
300 A
ORPL60A300
350 A
ORPL60A350
400 A
ORPL60A400
500 A
ORPL60A500
600 A
ORPL60A600
Effective 9/00