Wiring
Note: The Blue and
Black wires are ONLY
necessary if a in-ground
loop will be used
(Trigger Mode).
L o
n g
R F
R a
I D
n g
A n
e
t e n
n a
9 ft
Antenna
Cable
Note: Cable should be in
conduit for vandal protection.
SW1
Approximate
0
8 ft
Antenna
1
9.5 ft
2
11 ft
Reading
3
12 ft
Range
4
13 ft
5
14 ft
6
17 ft
7
19 ft
8
21 ft
9
25 ft
Use the rotary switch (SW1).
The reader will beep once
after each change of range. It
is also a good practice to put
the system into "test mode"
to benefit from the continu-
ous beeping feature while
adjusting the range.
SW2 DIP-switches 2, 3 and 4 MUST be set set to the ON position (right). This will put the
system in test mode. By choosing Timing/Trigger mode on DIP-switch 1, you can test in
either operating mode. Test mode is used to calibrate and adjust the maximum reading
range or maximum distance reader can read a tag/card. In timing test mode, reader sends
out read signals at a default rate of 10Hz. After each successful tag/card read, you will hear
a beep. As long as a tag/card is within range and in sight of the antenna, you will hear ten
beeps per second. This feature helps when adjusting the reader's reading range, using the
rotary switch SW1. In "trigger" test mode, the same is achieved in the presence of a valid
trigger signal (car on loop).
#10 - Black - Trigger Mode - for In-Ground Loop
#9 - Blue - Trigger Mode - for In-Ground Loop
#6 White - RXD (Receive Data)
#5 Purple - TXD (Transmit Data)
#4 Gray - D1 (Data 1)
#3 Yellow - D0 (Data 0)
#2 Black - Ground
#2 Black
2-Conductor
Power Cable
#1 Red
Orange
Brown
Not Used
1
2
3
4
5
6
8
9
10
12V
GND
D0
D1
TXD
RXD
GND
TRG
TRG
READER
RESET
SW1
DISTANCE
Long Range Reader Control Board
Test Mode
DoorKing 1830 Telephone Entry System Circuit Board
RS 232
1
2
3
4
5
6
MIC
VOL
3 2 1
SPK
VOL
FEED
BACK
3 2 1
HF
HS
RING
PHONE
CGND
PSW
MIC
COM
Note: 500 ft MAX length.
DO NOT use twisted wire.
#1 Green - D0 (Data 0) to #11 Aux
#2 White - D1 (Data 1) to #12 Aux
#3 Black - Ground to #13 Aux
#4 Red - N.O. - "Optional Loop Detector"
#5 Black - Ground - "Optional Loop Detector"
1
2
3
4
5
1
2
GND
TRG
TRG
D0
D1
12V
GND
CONTROL
POWER
Switches 5-8
NOT used:
set to OFF
Position
SW2
2362-010
ELEVATOR
Auxiliary
Terminal
ON
MASTER
CODE
OFF
KEYPAD
NO
NC
SPKR
IMD
5VDC
IMC
Z
A
2C
2RY
1C
1NC
1NO
BAT
16AC
16AC
Red - 12VDC
Black - Ground
SW2 DIP-Switch 1 Setting
Switch 1 OFF - Timing Mode
Switch 1 ON - Trigger Mode
Set for timing or trigger mode. See other side.
SW2 DIP-Switches 2-4 Settings
Switch 2
Switch 3
Switch 4
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
Set the reader to eliminate redundant readings
of the same tag/card at certain time intervals
by using SW2 DIP-switches 2, 3 and 4 (Note:
Switches 5-8 are NOT used). Example: If the
switches are set to: switch 2-ON, switch
3-OFF, switch 4-ON) the reader will read a
tag/card, beep and report it to the access
controller. For the next five (5) seconds, if it
reads the same tag/card again, it will ignore it.
It will not beep or report it to the access
controller.
Inglewood, California 90301
DoorKing Part Number
1815-350
"Optional" Trigger
Mode Wiring:
The
long range reader will
1
2
ONLY operate after the
3
trigger signal wires
have been activated by
a vehicle on the
in-ground loop.
V e
h i c
R
P W
L o
T
D E
l e
o p
IL
F A
D e
S E
T
R E
t e c
H
H IG
F
t o r
R
E
Q
W
L O
E Q
F R
Normally Open
(N.O.)
Dry Contact
Relay
12VDC
Power
Min
18 AWG
wire
100 ft MAX
Time Interval
ON
0 sec (Test Mode)
ON
1 sec
ON
5 sec
ON
10 sec
OFF
15 sec
OFF
20 sec
OFF
25 sec
OFF
30 sec