Alvarado MSGX-E Інструкція з монтажу та обслуговування - Сторінка 18

Переглянути онлайн або завантажити pdf Інструкція з монтажу та обслуговування для Огорожа та ворота Alvarado MSGX-E. Alvarado MSGX-E 20 сторінок. Full height maximum security gate

Troubleshooting

Symptom
Gate does not lock.
Gate does not unlock.
Page 18
Possible Cause
The gate is not powered (Fail-Safe units only).
The gate is still receiving an activation signal
from the gate activation switch.
The lock mechanism is misaligned.
The lock surfaces are obstructed or damaged.
The lock mechanism is defective.
The gate activation switch is defective.
The gate is not powered (Fail Lock units only).
The gate is not receiving an activation signal
from the gate activation switch.
The strike lock is sticking or binding in the
locked position. (Electric Strike units only).
The lock surfaces are obstructed or damaged.
The lock mechanism is defective.
The gate activation switch is defective.
For Assistance: [email protected] +1 (909) 591-8431
MSG Installation and Maintenance Instructions
Solution
• Confirm the power supply is plugged into
the appropriate VAC power source.
• Confirm the transformer output is 12VDC.
• Ensure that the gate activation switch is
properly connected to the gate activation
leads.
• Verify that the gate door and frame
installations are level.
• Adjust and realign the lock plate on the
gate door.
• Verify the lock surfaces on the gate door
and frame are free of debris.
• If the lock surfaces have been damaged,
replace the damaged components.
• Test and replace the lock mechanism as
necessary.
• Test and replace the gate activation switch
as necessary.
• Confirm the power supply is plugged into
the appropriate VAC power source.
• Confirm the transformer output is 12VDC.
• Ensure that the gate activation switch is
properly connected to the gate activation
leads.
• Verify that the gate door and frame
installations are level.
• Verify the lock surfaces on the gate door
and frame are free of debris.
• If the lock surfaces have been damaged,
replace the damaged components.
• Test and replace the lock mechanism as
necessary.
• Test and replace the gate activation switch
as necessary.
PUD1201R5-0