8- Table of parameters and messages
The Def. column indicates the ex-works configured default parameters. The pressure values featured on the table are expressed in bar and those for temperature in ºC. If the wizard meanwhile selects
another set of units (parameter C09), the equipment will make the conversion automatically.
INSTALLATION CONFIGURATION
Description
C01
Total number of compressors (with or without inverter)
CnF
C02
Number of stages per compressor
Polarity of the capacity reduction contact
C03
0=Active when closing the contact; 1=Active when opening the contact
C04
Compressor 1 with frequency inverter 0=No; 1=Yes
C05
Total number of fans (1 inverter only is considered with inverter)
C06
Fan control type 0=ON/OFF; 1=Frequency inverter
C07
Operation type 0=Direct; 1=Inverse
Refrigerant gas type
0=R134a 1=R404a 2=R717a 3=R22
C08
6=R744 7=R407a 8=R407f 9=R1234y 10=R448a 11=R449a 12=R450a
Display units (Primary-Secondary) 0=bar-ºC 1=psi-ºF
C09
3=bar-ºF 4=ºC-bar 5=ºF-psi
6=ºC-psi 7=ºF-bar
C10
Frequency inverter output type 0=4-20 mA; 1=0-10 V
InI
This indicates the configuration selected in the wizard (read only)
EP
Output to level 1
EVAPORATION CONFIGURATION
Description
E01
Pressure / evaporation temperature set point
EPr
E02
Evaporation set point upper limit (It cannot be set above this limit)
E03
Evaporation set point lower limit (It cannot be set below this limit)
Compressor rotation type: 0=Balancing, depending on the operation time
E04
1=Sequential (the last in is the first out)
E05
Compressor control type: 0=Neutral zone; 1=Proportional
E06
Evaporation regulation bandwidth
E07
Integral time (PID inverter control)
E08
Stop value for pump down (If C07=0)
E09
Maximum pump down time (If C07=0) (0= deactivated)
EP
Output to level 1
CONDENSATION CONFIGURATION
Description
F01
Condensation pressure / temperature set point
Cnd
F02
Condensation set point upper limit (It cannot be set above this limit)
F03
Condensation set point lower limit (It cannot be set below this limit)
Fan rotation type: 0=Balancing, depending on the operation time
F04
1=Sequential (the last in is the first out)
F05
Fan control type: 0=Neutral zone; 1=Proportional
F06
Condensation regulation bandwidth
F07
For fans when the compressors stop 0=No; 1=Yes
F08
Floating condensation 0=No; 1=Yes
F09
Integral time (PID inverter control)
F10
Floating condensation minimum set point value ( see remark 1)
F11
Condenser temperature delta
EP
Output to level 1
PROBE CONFIGURATION
Description
P01
Probe type selection 0=4-20 mA; 1=0-5 V; 2=NTC
Probe to be displayed: 0=Probe 1 (Aspiration)
CnP
P02
2=Probes 1 and 2 in carousel
P03
Value 4 mA / 0 V (according to P01) probe 1
P04
Value 20 mA / 5 V (according to P01) probe 1
P05
Probe 1 calibration (Offset)
P06
Value 4 mA / 0 V (according to P01) probe 2
P07
Value 20 mA / 5 V (according to P01) probe 2
P08
Probe 2 calibration (Offset)
P09
Calibration of the outside temperature probe for floating condensation
EP
Output to level 1
DIGITAL INPUT CONFIGURATION
Description
Polarity digital input 1 (thermal stage 1): 0=Activates on closing contact;
I01
Cni
Polarity digital input 2 (thermal stage 2): 0=Activates on closing contact;
I02
Polarity digital input 3 (thermal stage 3): 0=Activates on closing contact;
I03
Polarity digital input 4 (thermal stage 4): 0=Activates on closing contact;
I04
I05
Polarity digital input 5: 0=Activates on closing contact;
I06
Polarity digital input 6: 0=Activates on closing contact;
Digital input 5 function:
0=Low pressure alarm
I07
2=Thermal stage alarm 5 3=Ambient temperature probe 4=External alarm
5=Remote disconnection ON-OFF 6=Variation in the aspiration set point (E01) (see remark 2)
Digital input 6 function:
0=Low pressure alarm
I08
2=Thermal stage alarm 5 3=Ambient temperature probe 4=External alarm
5=Remote disconnection ON-OFF 6=Variation in the aspiration set point (E01) (see remark 2)
I09
Turn-on delay time of digital input 5 (not applicable if I07=2)
I10
Turn-on delay time of digital input 6 (not applicable if I08=2)
I11
Variation in the evaporation set point (new set point= E01+I11) (see remark 2)
I12
Duration of the variation in the evaporation set point (see remark 2)
EP
Output to level 1
ENERGY SAVING CONFIGURATION
Description
Start of energy saving - Day of the week: 0=Deactivated 1=Monday 2=Tuesday
S01
3=Wednesday 4=Thursday 5=Friday 6=Saturday
9=Monday to Saturday
10=Monday to Friday
ES
S02
Start of the energy saving - Hour (see remark 2)
S03
Start of the energy saving - Minute (see remark 2)
S04
Duration of the energy saving (see remark 2)
Variation in the evaporation set point during energy saving
S05
(E01+S05) (see remark 2)
Output to level 1
Read only parameters can only
be edited using the INI wizard.
Units
4=R410a 5=R507a
2=psi-ºC
Units
bar
bar
bar
bar
sec.
bar
sec. x 10
Units
bar
bar
bar
bar
sec.
ºC
ºC
Units
1=Probe 2 (Discharge);
bar
bar
bar
bar
bar
bar
ºC
Units
1=Activates on opening contact
1=Activates on opening contact
1=Activates on opening contact
1=Activates on opening contact
1=Activates on opening contact
1=Activates on opening contact
1=High pressure alarm
1=High pressure alarm
sec.
sec.
bar
min.
Units
7=Sunday 8=Monday to Sunday
11=Saturday to Sunday
h.
min.
h.
bar
Min. Def. Max.
Description
-
-
-
t01
Minimum operation time for a compressor
Tep
-
-
-
t02
Minimum disconnection time for a compressor
t03
Delay time between the compressor start-up/stage and the next one
0
0
1
t04
Delay time between the compressor stop/stage and the next one
-
-
-
t05
Minimum operation time for a fan
-
-
-
t06
Minimum disconnection time for a fan
-
-
-
t07
Delay time between the fan start-up and the next one
0
0
1
t08
Delay time between the fan stop and the next one
EP
Output to level 1
-
-
-
-
-
-
Description
A01
Number of active compressor stages with error in probe 1
0
0
1
AL
A02
Number of active fans or inverter % with error in probe 2
A03
Low pressure alarm in probe 1
A04
Low pressure alarm differential
Min. Def. Max.
A05
High pressure alarm in probe 2
E03
5
E02
A06
High pressure alarm differential
E03
75
75
A07
Alarm delay after reaching the value
-0.7
-0.7
E02
A08
Delay of temperature alarms in the start-up.
0
0
1
High pressure alarm limit (per digital input) per hour without manual reset. (If I07 or
A09
I08=1) (0=deactivated) Once the limit has been exceeded a manual reset will be required
0
0
1
for each new alarm.
0.0
2.0
50
EP
Output to level 1
2
5
10
-0.7
0.1
Description
0
0
255
r01
Hour
rtC
r02
Minutes
r03
Day
Min. Def. Max.
r04
Month
F03
19
F02
r05
Year
F03
75
75
EP
Output to level 1
-0.7
-0.7
F02
0
1
1
Description
P5
Address for units with communication
0
0
1
tid
L5
Access code (Password)
0.0
2.0
50
PU
Programme version
0
0
1
Pr
Check
0
0
1
EP
Output to level 1
2
5
10
-50
28
99.9
Description
6
12
20
c1
This shows the operation time for the compressor or fan 1
tFC
c2
This shows the operation time for the compressor or fan 2
c3
This shows the operation time for the compressor or fan 3
Min. Def. Max.
c4
This shows the operation time for the compressor or fan 4
0
0
2
c5
This shows the operation time for the compressor or fan 5
0
0
2
EP
Output to level 1
EP
Programming output
-60
-60
999
-60
999
999
* Dependin
g on the compressor control type: Proportional=E01; Neutral zone=E01-E06.
-20
0
20
** If the compressor is equipped with an inverter, this period of time halves.
-60
-60
999
*** The number of st
-60
999
999
Remark 1: The equivalent value in pressure is calculated depending on the refrigerant gas
-20
0
20
specified in the wizard.
-20
0
20
Remark 2: In the event of the energy saving and the variation in the set point per digital input
being activated at the same time, the variation in the set point per digital input will
always prevail.
Min. Def. Max.
MESSAGES
0
0
1
L5
Access code (Password) request
0
0
1
PdA
Pump down detained due to time
Ar
Clock battery dead or clock deprogrammed
0
0
1
ALL
Low pressure alarm due to probe 1
ALH
High pressure alarm due to probe 2
0
0
1
At1
Thermal alarm 1
0
0
1
AT2
Thermal alarm 2
0
0
1
At3
Thermal alarm 3
At4
Thermal alarm 4
0
0
6
At5
Thermal alarm 5
AES
Severe external alarm (input I5 or I6)
0FF
Remote regulation detained due to digital input (input I5 or I6)
0
1
6
LPA
Low pressure alarm due to digital input (input I5 or I6)
High pressure alarm due to digital input (input I5 or I6)
HPA
0
0
255
E1
Error in probe 1 (open circuit, probe crossed or out of range)
0
0
255
E2
Error in probe 2 (open circuit, probe crossed or out of range)
-20
0
20
E3
Error in probe 3 (open circuit, probe crossed or out of range)
0
0
255
D: The message is shown on the display.
Min. Def. Max.
R: Alarm relay activated (if available, see WIZARD table).
0
0
11
0
0
23
0
0
59
0
0
24
-20
0
20
TIMING CONFIGURATION
**
CONFIGURATION OF PROTECTIONS AND ALARMS
DATE AND TIME CONFIGURATION
ACCESS AND INFORMATION CONTROL
OPERATION TIMES
ages depends on the configuration selected in the wizard.
Units
Min. Def. Max.
sec. x10
1
2
999
sec. x10
1
2
999
sec.
1
30
999
sec.
1
10
999
1
1
999
sec. x10
sec. x10
1
1
999
sec.
1
2
999
sec.
1
2
999
Units
Min. Def. Max.
0
0
Without inverter
0
C05
C05
With inverter
0
100% 100%
bar
-0.7
0
75
bar
0.1
1.0
20
bar
-0.7
20
75
bar
0.1
1.0
20
0
60
999
sec.
sec.
0
0
255
0
0
255
Units
Min. Def. Max.
00
00
23
00
00
59
1
1
31
1
1
12
00
15
99
Units
Min. Def. Max.
1
1
255
0
0
999
-
-
-
-
-
-
Units
Min. Def. Max.
hours x10
-
-
999
hours x10
-
-
999
hours x10
-
-
999
hours x10
-
-
999
hours x10
-
-
999
D -
D -
D -
D R
D R
D R
D R
D R
D R
D R
D R
D -
D R
D R
D R
D R
D R