MODEL 6700 Downflow - V2.0
Option Setting Level #2
Softener Manufacturer Programming (Cont'd.)
17. Mixing Valve Location (8)
Depress the Program Button. The next display is used
to set where the mixing valve is located, if any. It is
viewed only with the U.S./Metric Display Format set to
U-2 or U-4. There are three possible settings:
Examples: [8 - - - - - 1] No Mixing Valve
[8 - - - - - 2] Mixing Valve Before Flow
Meter
[8 - - - - - 3] Mixing Valve After Flow
Meter
The UP and DOWN Set Buttons will adjust this
value.
18. System Type (9)
Depress the Program Button. The next display viewed
is an option setting. This display is used to set the
type of system the valve is operating in. There are six
possible selections with #4 the desired setting:
Single Valve Meter or Sensor Regeneration -
When this option is selected, the control will operate
as a stand alone unit. The control can initiate a
regeneration whenever needed.
Example:
[9 - - - - - 4] Single Valve Meter or Sensor
Regeneration (System #4) Operation
[9 - - - - - 5] Option Not Typically Used
[9 - - - - - 7] Option Not Typically Used
[9 - - - - - 9] Option Not Typically Used
The UP and DOWN Set Buttons will adjust this
value.
19. Program Lock (PL)
Depress the Program Button. The display is used to
prevent certain displays from being viewed or set.
There are two possible settings:
Examples: [PL - - - OFF] Lock Cancelled
[PL - - - - ON] Lock Active
Settings Able To Be Reset With Protection Active
-Displays Able To Be Viewed With Protection
Active -
Water HardnessFlow Rate Display
Water Hardness After Mixing ValveDays Since
Regeneration Display
Regeneration TimePrior Service Volume Used
Display
Time of DayReserve Capacity Display
Previous Days Water Usage Display
Unlocking Programming -
The only way to deactivate this feature is to push and
hold the Program Button for 25 seconds. This
procedure will unlock the control and permit all valid
program settings to be viewed and reset as needed.
The UP and DOWN Set Buttons will adjust this
value.
Exiting This Option Setting Level
Push the Program Button once per display until all have
been viewed.
Resetting Permanent Programming Memory -
Push and hold the Program Button for 50 seconds. This
procedure will erase this and all previous display settings
and reset them to default values. Control programming
will then have to be reset as necessary.