ETA Systems ETA-ECM2063 Посібник - Сторінка 5

Переглянути онлайн або завантажити pdf Посібник для Блок розподілу електроенергії ETA Systems ETA-ECM2063. ETA Systems ETA-ECM2063 16 сторінок. Ac power distribution sequencer raceway system

INTRODUCTION

Thank you for purchasing the ETA Systems ETA-ECM2063 AC Power Distribution Sequencer Raceway System. The ETA-ECM2063 is
designed to offer the installer/contractor current requirement flexibility based on the needs of the equipment that will be connected
to the raceway. The ETA-ECM2063 accepts up to three separate 20A 120VAC lines, allowing for up to a total of 60A to be divided
throughout the system. The ETA-ECM2063 features 6 individual AC 120V outlet sections that can be activated individually or in a
sequenced order. Triggering a section or sequential order can be accomplished via a remote switch or by using a sequence controller
like the ETA Systems ETA-SEQ6 or ETA-ECS6RM.
The ETA-ECM2063 features a total of 12, 120VAC outlets that are divided into 6 sections. Each section has an activation control port
and a bi-color LED. This LED will display green to indicate that AC voltage is present at that specific AC section when it is activated or
triggered and the LED will display red to indicate that the section is in Stand-By mode.
Activation has been made easy, simply short the two pins of the control port for the specific channel you want triggered ON. This can
be accomplished within a few feet of the ETA-ECM2063 or from several feet away by using an ETA Systems sequence controller or via
a switch.
The ETA-ECM2063 was designed to be compact measuring only 37" high, 3.5" wide and 2.75" deep. The ETA-ECM2063 can be
mounted into most racks that have 48" internal height. The raceway can be mounted using the raceway mounting tabs which are
designed to breakaway if needed to fit into tighter areas making it adaptable to secure the raceway in most applications. For your
convenience there are six
" &
1
2
the raceway housing from the electrical panel. Note: For your safety all electrical wiring must be done by a qualified electrician.

KEY FEATURES

• Compact design 37"H x 3.5"W x 2.75"D
• 6 Separate 120V Outlet Sections
• 12, 120VAC 20A Outlets
• Accepts up to 3 20A 120VAC Lines, Configurable
• Incoming AC present LED
• Active LED
• Remote or Local Activation
• Hard Switch Contact Closure Trigger
• 6 Dual Knockouts
" &
1
2
• 4 Rail Mounting Tabs

APPLICATIONS

The ETA Systems ETA-ECM2063 was designed to be flexible, incorporating features that allow it to be used in a variety of applications.
The sequenced outputs allow equipment to be turned ON or OFF in a particular order. This prevents an in-rush of current that could
potentially damage connected electronics and eliminates audible pops that often occur with non-sequenced power activation. The
following are just a few examples of applications in which the ETA Systems ETA-ECM2063 can be used:
• Restaurants
• Houses of Worship
• Schools
• Home Theaters
• Office Buildings
• Sports Bars
• Industrial Facilities