3 Installation requirements
The fire
− Always place the appliance with a minimum distance of 1000[mm], 100[cm], 1[meter] from
combustible objects or materials.
− Place the discharge pipes in such a way that situation with the risk of fire could never occur.
− Always place the appliance in front of a wall of a non-combustible and heat-resistant material.
− Take sufficient measures to prevent temperatures of a wall behind the chimney breast becoming
too high, including the materials and/or objects behind the wall.
− Do not cover the appliance an d/or do not wrap it in an insulation blanket or any other material.
− Make sure that the appliance is installed in a stable position.
− Provide a gas connection at the location.
− The appliance must be built into an existing or a newly to be constructed false chimney breast.
− In appliances with flexible gas pipes, the gas control valve is mounted to the right side of the fire for
safe transport. Unscrew it and mount it at a distance of max. 30 cm behind the access door.
− The receiver which has been attached in a transport holder (see fig. 1.4 A) to the side of control
valve bracket can now be slid onto the top of the control valve bracket. The transport holder can be
removed now.
False Chimney breast (IF applicable)
− The false chimney breast must be constructed of a non-combustible material.
− Always ventilate the space above the appliance by means of the grills or a comparable alternative
with a minimum air supply of 400 cm², supplied through ingoing and outgoing ventilation holes. The
outgoing, discharge ventilation holes must be as high as possible in the chimney breast.
− Ventilation holes design is up to the designer. The designer must take into account the minimum
surface area of 400cm²
− Take sufficient measures to prevent temperatures of a wall behind the chimney breast becoming
too high, including the materials and/or objects behind the wall.
− When the appliance is built in the floor, please take into account the minimum distance from a
combustible floor.
− Use noncombustible and heat resistant materials for the chimney breast, including the top of the
chimney breast, the material in the chimney breast, and the back wall of the chimney breast.
− For the finish, use special stucco (min. 100°C resistant) or glass fiber wallpaper to prevent
discoloration or cracks etc. Recommended drying time: for plaster is a minimum of 24 hours per
mm of coat applied.
− Location of ventilation holes, the outgoing ones, must be as high as possible.
− Make sure that the appliance is not carrying the weight of the chimney breast; the chimney breast
construction must not rest on the appliance.
Control hatch (IF applicable)
− Place the control hatch as low as possible in the chimney breast.
− The bottom of the control hatch must not be higher than the burner surface of the fireplace.