Connecting an Open Collector Pulse Output device
The term
open-collector
typically refers to a transistor output where the collector (output) of the transistor is not connected to a positive
voltage. Since a transistor used in outputs is a saturated switch, the collector needs to be connected to a positive voltage to complete the
transistor circuit. This positive voltage need not be any specific value as long as it is above the saturation of the transistor. Because of this, an
open collector output can be connected to a range of voltages using a pullup resistor. This resistor is required for the output to function as it
completes the transistor's circuit.
Many circuits use open-collector outputs to be able to provide Different Voltage Interfacing
Since the exact voltage of the pullup resistor is not critical, an open-collector output can be used to interface one logic voltage level with
another.
Supply +V1
8-2 Vdc
4
Red
UFunit
Circuit using different voltages
Connecting a 4-20mA Output device
4-20mA Standard
4-20mA output systems are an industrial control standard as they allow input signal changes, without affecting the output current. This also
means that the output signal is relatively immune to noise (as most noise will cause voltage disturbances, and not affect the regulated
current). This makes 4-20mA devices more suited to critical-control systems.
Cable Connection
s -
Red: Power Supply +ve connection Black: Common
Excessive Load Resistance will cause current sourcing that will affect the accuracy of this device's current output.
Note:
There is no requirement for a minimum Load resistance, as this is a current sink device
Supply +V
(8-24Vdc)
Power Supply
Sensor
Black
Common
An ammeter (or suitably arranged multi-meter), placed in series at the Iout point, will give an indication of the sensors current performance i.e.
flow.
If the meter used has adjustable zero and span, then the meter could be altered to represent the flow in litres/min.
9001
ISO
C E R T I F I E D
© 2014 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
Supply +V2
5-2 Vdc
10kR
Blue
Counter
Black
,
Maximum Load Impedance:
Red +V
I
UF
Brown
Current Sink
4-20mA
4
UFunit
, Brown
: Current Sink (4-20mA)
R L = Vin -
(
Iout
Red
10kR
Blue
Black
Circuit using common voltage supply
5) x 40
R
Load(circuit)
www.cynergy3.com
Supply +V
8-2 Vdc
4