Ashcroft AUF Інструкція користувача - Сторінка 4
Переглянути онлайн або завантажити pdf Інструкція користувача для Монітор Ashcroft AUF. Ashcroft AUF 5 сторінок. Compact local electronic display
6.3 Range (value to be displayed at 20 mA)
Press B key until E P 2 0 is displayed
=>A+B menu item to set - 0 0 0
=>B or A for up and down 6 0.0 0 (60 psig)
=>A+B to confirm setting and return to menu item - E P –
6.4 Attenuation
Press B key until F I L t is displayed
=>A+B menu item to set 0 0 0.3 (Min.=0.3 sec.;Max.=20.0 sec.)
=>B or A for up or down - - 1.5 (1.5 sec.)
=>A+B to confirm setting and return to menu item F I L t
6.5 Range Exceeded (displayed if below 4 mA or above 20 mA)
Display: "HI"=>range exceeded or "L0"=>below range
Press B key until H I L 0 is displayed
=>A+B menu item for setting: - 0 F F display inactive
=>B or A for up or down: - 0 n - display active
=>A+B to confirm setting and return to menu item H I L 0
Report - h I - = measuring range exceeded, - L 0 - = below measuring range
Please note: If H I L 0 display is inactive, measuring range exceeded (-1999 to 9999) is indicated by
"E r 0 6"
6.6 Operating Position (Option)
Press B until - S P t is displayed
=>A+B menu item for setting - 0.0 0
=>B or A for up or down: 2 0.0 0 (20 psig)
=>A+B to confirm setting and return to menu item - S P t
Please note: Standard hysteresis is the set point minus 3 digits
Upon customer request, the hysteresis is adjustable at the plant as per request
4
Rev. Jan. 2002