DOLD INFOMASTER SMS RP 5812 Методика моніторингу - Сторінка 4
Переглянути онлайн або завантажити pdf Методика моніторингу для Блок управління DOLD INFOMASTER SMS RP 5812. DOLD INFOMASTER SMS RP 5812 4 сторінки. Sms-telecontrol module
Accessories
OA 5810/900:
OA 5810/901:
Fault indicated by Flashing Code
The current state of the SMS-Telecontrol module is indicated by the flashing
code on the status LED. The number of flashing pulses followed by a longer
space relates to the failure code in the following table. After the longer space
the flashing cycle is repeated until the state on the unit changes.
State LED
Description
OFF
No status for indication, normal operation
ON
SMS transmission
Internal system failure,
2 * flashes
please contact the manufacturer
Invalid configuration. When this failure occurs, the unit
tries to reset the configuration to factory settings followed
3 * flashes
by a device test. If the failure remains, please contact
manufacturer.
No access on SIM-card
4 * flashes
Cause:
no SIM-card inserted or
invalid PIN for inserted SIM card
No GSM network available
Cause: insufficient radio signal, aerial placed
5 * flashes
in a poor location.
In the configuration, the service centre for SMS transmis-
sion is not yet defined.
6 * flashes
Cause: The CFGINT command sequence SMS has not
been sent to the module
No administrator for using are defined.
No user administrator is defined
7 * flashes
Cause: The CFGINT command sequence SMS has not
been sent to the module
LEDs for each I/O on the front of the unit indicate the status of the in- and
outputs.
E. DOLD & SÖHNE KG • D-78114 Furtwangen
e-mail: [email protected] • internet: http://www.dold.com
GSM-aerial, 90° angle
Article number:
0062212
GSM magnetic foot areal with 2,5 m
connecting lead
Article number:
0062213
•
PO Box 1251 • Telephone (+49) 77 23 / 654-0 • Telefax (+49) 77 23 / 654-356
4
22.02.13 en / 313