Ambirad AMBITEC PLUS Handbuch - Seite 8

Blättern Sie online oder laden Sie pdf Handbuch für Bedienfeld Ambirad AMBITEC PLUS herunter. Ambirad AMBITEC PLUS 11 Seiten. Energy saving electronic control panel

AMBITEC
AR
AR
AR
ARE
ARE
ARE
SERIES
SERIES
SERIES
/
/
/
8 Relay switching
Timer OFF
Heat
=
Night mode
Vent
=
Frost mode
Auto
=
Night mode
OFF
=
Frost mode (including holiday shutdown)
Timer ON
Heat
=
Heat mode
Vent
=
Vent mode
Auto
=
Auto mode
OFF
=
Frost mode
Frost mode
CRF
=
On if H1 is ON
H2
=
On if room temperature < than frost temperature setting +2˚C
H1
=
On if room temperature > than frost temperature setting
V1
=
OFF
V2
=
OFF
V3
=
OFF
0 - 5VDC output
=
ON if H1 is ON
Heat mode
CRF
=
ON
H2
=
ON if room temperature is < daytime temperature setting -2˚C
H1
=
ON if room temperature is > daytime temperature setting
V1
=
OFF
V2
=
OFF
V3
=
OFF
0 - 5VDC output
=
ON if H1 is ON
Vent mode
CRF
=
ON
H2
=
OFF
H1
=
OFF
V1
=
ON if room temperature > than day setting temperature + dead band setting
V2
=
ON if room temperature > than day setting temperature + dead band + 2˚C
V3
=
ON
0 - 5VDC output
=
OFF
Auto mode
CRF
=
ON
H2
=
OFF if room temperature > day temperature setting -2˚C
H1
=
OFF if room temperature > day temperature setting
V1
=
ON if room temperature > day temperature setting + dead band
V2
=
ON if room temperature > day temperature setting + dead band +2˚C
V3
=
ON/OFF as programmed
0 - 5VDC output
=
ON
Flame reset
01
=
All relays OFF
02
=
CRF + H1 + H2 + reset ON
6
PLUS
ENERGY SAVING ELECTRONIC CONTROL PANEL