8 Relay switching
Timer OFF
Heat
=
Night mode
Vent
=
Frost mode
Auto
=
Night mode
OFF
=
Frost mode (including holiday shutdown)
Timer ON
Heat
=
Heat mode
Vent
=
Vent mode
Auto
=
Auto mode
OFF
=
Frost mode
Frost mode
CRF
=
On if H1 is ON
H2
=
On if room temperature < than frost temperature setting +2˚C
H1
=
On if room temperature > than frost temperature setting
V1
=
OFF
V2
=
OFF
V3
=
OFF
0 - 5VDC output
=
ON if H1 is ON
Heat mode
CRF
=
ON
H2
=
ON if room temperature is < daytime temperature setting -2˚C
H1
=
ON if room temperature is > daytime temperature setting
V1
=
OFF
V2
=
OFF
V3
=
OFF
0 - 5VDC output
=
ON if H1 is ON
Vent mode
CRF
=
ON
H2
=
OFF
H1
=
OFF
V1
=
ON if room temperature > than day setting temperature + dead band setting
V2
=
ON if room temperature > than day setting temperature + dead band + 2˚C
V3
=
ON
0 - 5VDC output
=
OFF
Auto mode
CRF
=
ON
H2
=
OFF if room temperature > day temperature setting -2˚C
H1
=
OFF if room temperature > day temperature setting
V1
=
ON if room temperature > day temperature setting + dead band
V2
=
ON if room temperature > day temperature setting + dead band +2˚C
V3
=
ON/OFF as programmed
0 - 5VDC output
=
ON
Flame reset
01
=
All relays OFF
02
=
CRF + H1 + H2 + reset ON
6
PLUS