8. MY BREAKER IS POPPING.
Your breaker may be undersized . Check sizing requirements for your current setup . If further assistance is
needed in sizing, contact American Rotary .
Make sure your wire is big enough . Step-up at least one size for every 50 feet of run . Wire may need to be
upsized for hard loads .
9. MY VOLTAGE IS NOT BALANCED.
Do not measure line to ground . T3, the manufactured line, references a floating ground . The output of a
phase converter is a Delta three phase voltage . If a neutral or 120 volts to ground is needed from all three
lines, a Delta-Wye transformer is needed . American Rotary stocks the correct transformers for this .
Make sure to check the voltage under load as it will be more balanced at that time .