American Rotary AMP 10 Manual do utilizador - Página 14

Procurar online ou descarregar pdf Manual do utilizador para Transformador American Rotary AMP 10. American Rotary AMP 10 18 páginas.

8. MY BREAKER IS POPPING.
Your breaker may be undersized . Check sizing requirements for your current setup . If further assistance is
needed in sizing, contact American Rotary .
Make sure your wire is big enough . Step-up at least one size for every 50 feet of run . Wire may need to be
upsized for hard loads .
9. MY VOLTAGE IS NOT BALANCED.
Do not measure line to ground . T3, the manufactured line, references a floating ground . The output of a
phase converter is a Delta three phase voltage . If a neutral or 120 volts to ground is needed from all three
lines, a Delta-Wye transformer is needed . American Rotary stocks the correct transformers for this .
Make sure to check the voltage under load as it will be more balanced at that time .
14 | User Manual R2 .3