Mechanical And Plumbing Installation
Positioning
The AKW M11 DigiPump shower waste water pump must be installed by a
suitably qualified, competent person eg. NIC EIC, in accordance with current IEE
Wiring Regulations (BS7671), building regulations and local by-laws.
This product is rated at IP45 and suitable to be installed in Zone 1 or Zone 2
of a shower room only if these instructions are fully complied with.
The unit must be located away from the direct line of water jets.
Note: Zone 1 lies above zone 0 and below 2250mm (88in) vertically above a shower
tray or wet floor area.
The perimeter of zone 1 of a wet floor is within a 1.2 metres (47in) radius of the
shower head position. Consult BS7671 for further clarification.
FOR GUIDANCE ONLY- PLEASE REFER TO BS7671 FOR FURTHER DETAILS