Baumer GIM500R Handbuch - Seite 10
Blättern Sie online oder laden Sie pdf Handbuch für Zubehör Baumer GIM500R herunter. Baumer GIM500R 20 Seiten. Inclination sensors
Auch für Baumer GIM500R: Handbuch (29 seiten), Handbuch (13 seiten), Montageanleitung (2 seiten)
Analog output with sensing range monitoring (Option: /4822)
3.3.4
Sensor behavior with option /4822 sensing range monitoring is as follows: the output value jumps to a higher
respectively lower value compared to nominal voltage or nominal current.
Outside the sensing range, the output value jumps from the maximum to the minimum signal value at half
the rotation angle (see 3.3.1Analog output signals) When the sensor is inclined towards the opposite
direction the value jumps from the minimum to the maximum signal value.
Overview output signals
Analog
Output
Interface
Underrange
0...5 V
0 V
0...10 V
0 V
4...20 mA
2 mA
0...20 mA
0 mA
0...24 mA
0 mA
0.5...4.5 V
0 V
Analog output with sensing range monitoring 1-dimensional
Measuring range 0...90° / 0.5...4.5V
Measuring range 0...180° / 0...10 V (0...5 V)
Baumer_GIM500R_Analog_MA_EN.docx
11.04.18
Output
Out of Range
Overrange
Diagnostic
5.5 V
Overrange
11 V
Overrange
22 mA
Underrange, Overrange
22 mA
Overrange
24 mA
None
5 V
Underrange, Overrange
10/20
Baumer IVO GmbH & Co. KG
Villingen-Schwenningen, Germany