2.4.7 Typical Host Panel Monitoring/Control of the AX-CZM Module

Note: The HOST FACP normally open (momentary closed for reset) input is unsupervised, wiring must be
within 20 feet of the reset contact in conduit. Supervision of the alarm, trouble and, if required,
earth/ground relay contacts is performed by the Host FACP zone modules. The trouble relay contact, is
failsafe (inverted) loss of 24 VDC power will transfer the trouble contact. End-of-line resistors for the
Canadian CAX-CZM must be installed on an Advanced EOL-ASSY (standard single gang end-of-line plate).
Preconfigured "Non-Latching" zone circuits (Class B = zones 5 & 6; Class A = zone 4) are not permitted by
ANSI/UL864 or ULC S527. These zones should be considered Not Connected.
14