(2) After wiring is complete, clamp the remote controller cable, transmission cable and
power supply cable with binder.
For U.S.A. and Canada
For Others
When installing a screw on the terminal block, do not cut the cable by overtightening
the screw. On the other hand, an under tightened screw can cause faulty contact,
which will lead to a communication failure.
(3) Attach the control box cover.
En-9
Binder (Medium)
(Accessories)
Remote controller cable
Y1: Red
Y2: White
Y3: Black
X1, X2:
Transmission cable
GND
Conduit
(L1, L2 (N): Power supply
Lock nut
cable)
Binder (Medium)
(Accessories)
Remote controller
cable
Y1: Red
Y2: White
Y3: Black
X1, X2: Transmission
cable
Binder (Medium)
(Accessories)
Grommet edging
(Accessories)
L1, L2 (N): Power supply cable
CAUTION
] 1

6.5. External input and external output (Optional parts)

Controller PCB
Output
terminal
(CN24)
(1) External input terminals
• Indoor unit can be Start/Stop or Emergency stop by using indoor unit PCB CN27.
Wiring methods and specifi cations
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft. (25 m)
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
• Open circuit voltage : ≤ 5.25 (V).
• Short circuit current : ≤ 0.6 (mA).
• Short circuit detection resistance (R ON) : ≤ 500 (ohm).
• Short circuit detection resistance (R OFF) : ≥ 100 (kilo-ohm).
*
*
Ch 2
Ch 1
Connected unit
* Select very low current use contacts (usable at DC12V, DC1mA or less).
When connected to no voltage terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
When connected to multiple indoor units directly, it will cause breakdown.
Input device 1
Input device 2
Output
Output
terminal
terminal
(CN23)
(CN22)
Input
terminal
(CN27)
P.C.B
1
2
3
GND
P.C.B
K1
K4
CN27
P.C.B
K2
K5
CN27
P.C.B
K3
K6
CN27
K1-K6: Relay
(Device for DC Current)
CN27