Carlyle 05T-033 Anwendungshandbuch - Seite 10
Blättern Sie online oder laden Sie pdf Anwendungshandbuch für Kompressor Carlyle 05T-033 herunter. Carlyle 05T-033 20 Seiten. Screw compressor
be located upstream to ensure positive shut-off when the
compressor is off.
R-448A, R-449A, R-404A &
Compressor
Model
Low Temp.
Low Temp.
90°F to 120°F
SCT Range
(32°C to 49°C)
06TRC033
EA02ZD001*
06TRD039
EA02ZD002*
06TRD044
EA02ZD002*
06TRE048
EA02ZD030*
06TRE054
EA02ZD050*
06TRF065
EA02ZD050*
06TRG078
EA02ZD050*
06TRH088
EA02ZD050*
06TRK108
EA02ZD050*
Med Temp/High Temp
SCT Range
06TAD033
06TAE039
06TAF044
06TAF048
06TAG054
06TAG065
06TAH078
06TAK088
* Operation with Evap. condensers below -25°F (-32°C) SST
may not require any additional desuperheating. Contact Carlyle
Application Engineering for limits.
**Operation with Evap. condensers above +10°F (-12°C) SST
may not require any additional desuperheating. Contact Carlyle
Application Engineering for limits.
10
DESUPERHEATING VALVE SIZING WITHOUT OIL COOLER
R-507
Med Temp.
Low Temp.
70°F to 120°F
EA02ZD030
EA02ZD050
EA02ZD050
EA02ZD050
EA02ZD050
EA02ZD100
EA02ZD100
EA02ZD100
EA02ZD100
70°F to 130°F
(21°C to 34°C)
Not Required
The tables presented at the bottom of this page present de-
superheating valve size and part number information for
those applications where an oil cooler is not used.
R-22
Med/High
Temp.
(21°C to
49°C)
70°F to 130°F
(21°C to 54°C)
EA02ZD030**
EA02ZD050**
EA02ZD050**
EA02ZD050**
EA02ZD050**
EA02ZD100**
EA02ZD100**
EA02ZD100**
NOTE: A valve with a 190°F(88°C) temperature setting is
required. Alternate desuperheating valve sizing or manufactur-
ers must be approved by Carlyle Application Engineering.
R-134a
Medium Temp.
High Temp.
70°F to 150°F
70°F to 150°F
(21°C to 65°C)
(21°C to 65°C)
Not Required
Not Required
Not Required
Not Required