Atkinson Electronics GSCM-mini-P Handbuch - Seite 10
Blättern Sie online oder laden Sie pdf Handbuch für Kontrolleinheit Atkinson Electronics GSCM-mini-P herunter. Atkinson Electronics GSCM-mini-P 18 Seiten. Generator start control module
LED Description and Meanings
Start:
Generator Hz Shutdown
Run
Fault
K1 & K2
Specifications
Size:
5.13" L x 2.853" W x 1.35" H
Weight:
20oz.
Mounting:
2 screws through tabs
Power:
12VDC Battery
9.5 to 15VDC
Quiescent current < 10mA
Relay current < 25mA each
Manual Input:
B+ (12VDC) input = on condition
Open input = off condition
Battery Input:
0-60VDC
Auto Start/
Stop Threshold:
12V System 11.5V, 13.8V
24V System 23.0V, 27.6V
48V System 46.0V, 55.2V
Relay
Configuration:
Open input = momentary crank
(Terminal 6)
Grounded input = maintained crank
B+ (12VDC) input = ignition & crank
Ambient Temp:
-40 to 85°C
www.atkinsonelectronics.com
Circuit Board Division
800.261.3602
One blink every 5 seconds = ready mode, looking for a start signal
One blink every 2.5 seconds = auto start mode operation
One blink every other second= auto start/stop period
Continuous = manual start signal received
Fast blink = 60 second delay after start signal removed before generator started
Fast blink = over speed condition
Slow blink = under speed condition
Double blink = maximum crank attempts reached, failed to start
Triple blink = auto start attempted with-in 30 minutes of a max run time (6 hour ) shutdown
Four blinks every 2 seconds = AC Hz or 12V run status signal lost during run mode
Continuous = start function disabled, AC Hz detected while in ready mode
Continuous = GSCM-mini has a valid run signal from generator
Continuous = GSCM-mini is in a fault condition and requires a reset
Continuous = status of K1 and K2 relays on
Gen. Hz Enable:
(Terminal 8)
Frequency Input:
(Terminals 9 & 10)
Output Ratings:
Fault Detection:
10
Open input =
Generator Hz shutdown not active
Grounded input =
Generator Hz shutdown active
12VDC input =
Generator run Status input
Over/under Hz shutdown
not active
24VAC, 120VAC & 240VAC 0-100 Hz
Two 10 AMP 28VDC relay contacts,
K1 has 38VDC MOV across contact.
Two open collector NPN transistors,
maxium 300mA each
Start failure, (3 attempts)
Over Hz condition (10 seconds)
Under Hz condition (10 seconds)
Max run time (6 hours)
Loss of AC Hz or 12V run status signal
Revised 02/21