Andivi – TRC-D – Technical Manual
ENGINEER MODE MENU ITEMS DESCRIPTION
Item Mnemonic
1
ESIC
Protect (PROT) Cooling set-point
2
ESIH
Protect (PROT) Heating set-point
Locking buttons and functions
Bit Value:
0: Unlock / enable
1: Lock / disable
Bit Definition:
Bit 0: Local PROTECT
detection
Bit 1: MODE button
3
LOC
Bit 2: UP/DOWN
button
Bit 3: FAN SPEED
button
Bit 4: ON/OFF button
Bit 5: Local Economy
detection
Bit 6: Engineer mode
Bit 7: Not used
4
baud
Baud rate
5
Prty
Parity / Data / Stop bits
6
nodE
Modbus Node ID
7
Unit
Unit
8
type
Type of room controller
9
db
Deadband for Cooling/Heating valve control 4.0
10
Pb
Not used
11
diFF
Stage differential
12
SP-L
Low limit for temperature set-point
13
SP-H
High limit for temperature set-point
14
ESI
PROTECT contact definition
15
OFSt
Offset for built-in temperature sensor
16
rS
Source of temperature sensor
17
F-Pb
Proportional band for fan control
18
i-db
Not used
19
LFAn
Lowest fan speed used for fan auto mode
Display present value of temperature or set-
20
PvLC
point for normal displaying
21
PtCF
Present temperature to anti-freezing
22
AntF
Anti-Freezing Protection
23
I-t
Not used
24
Pit
Period of sensor suffocating time
25
ESI2
Economy contact definition
26
EoSt
Offset for external temperature sensor
27
ES2C
Economy (ECON) Cooling set-point
28
ES2H
Economy (ECON) Heating set-point
29
Fand
Fan off delay
11
08/14, fw. ver. V1.2, V1.3
Description
Examples:
0: Unlock / enable all
1: Disable Local
PROTECT
2: Lock MODE button
3: Both 1 and 2
4: Lock UP/DOWN
button
5: Both 1 and 4
7: 1, 2, and 4
8: Lock FAN SPEED
button
16: Lock POWER
button
127: Lock/disable all
°C Type
Default
Range
30.0
20.0~40.0
86.0
15.0
00.0~25.0
59.0
18
18
(Lock
(Lock
MODE
MODE
0~127
and
and
POWER
POWER
buttons)
buttons)
2400 bps
4800 bps
19200
19200
9600 bps
19200 bps
8O1
8E1
8N2
8N2
8N1
8N2
247
1~247
247
°C
°C/°F
°C
E-type
B,C,E
E-type
0~10.0
7.2
0.5
0.1~1.0
0.9
10.0
0~50.0
50.0
30.0
0~50.0
86.0
1
0~1
1
0.0
-9.0~9.0
0.0
0
0~2
0
4.0
0~10
7.2
0
0~1
0
0
0~1
0
10
0~15
50
On
On/Off
On
20
0~120
20
1
0~1
1
0.0
-9.0~9.0
0.0
27.0
20.0~40.0
80.6
18.0
00.0~25.0
64.4
0
0~600
0
°F Type
Default
Range
68.0~104.0 0.1°C/°F
32.0~77.0
0.1°C/°F
0~127
1
2400 bps
4800 bps
9600 bps
19200 bps
8O1
8E1
8N1
8N2
1~247
1
°C/°F
B,C,E
0~18.0
0.1°C/°F
0.1~1.8
0.1°C/°F
32.0~122.0 0.1°C/°F
32.0~122.0 0.1°C/°F
0~1
0: N.O. / 1: N.C.
-17.0~17.0 0.1°C/°F
0: Built-in /
1: Remote
0~2
2: Built-in +
remote
(average)
0~18
0.1°C/°F
0: Stop /
0~1
1: Low speed
0: Display PV /
0~1
1: Display SP
32~59
0.1°C/°F
On/Off
0~120
1 sec.
0~1
0: N.O. / 1: N.C.
-17.0~17.0 0.1°C/°F
68.0~104.0 0.1°C/°F
32.0~77.0
0.1°C/°F
0~600
10 sec.
Step