Assembly instructions
3P Volume Filter VF12 - installation
Installation
It is recommended to have the filter installed in the factory.
For installation in the shaft, we recommend pushing short sleeve pieces corresponding to the
specified diameters from the outside through the hole into the appropriate filter connections.
This avoids the connecting pipes shifting or the seals warping when assembling on the building
site.
If connecting directly on the building site, please ensure that the seals are seated cleanly.
The pipe sections should not project any further than 3.14" into the filter.
For the sealing of the drill holes in the shaft we recommend Forsheda seals.
The filter itself should be vertically levelled.
Compensation rods are included, with which small differences can be compensated.
The shaft must be inserted evenly. The shaft bottom should have a downward gradient of approx.
5% towards the sewer connection. This allows dirt deposits to be washed away well.